| 2020-07-10 10:35:36 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK | | | SHALL COMPLY WITH THE MATERIALS AND METHODS | | | REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | | | | | | 1-- FLAT ROOF NOA 20-0131.01 SUBMITTED: SELECTED | | | ASSEMBLY ON PAGE 12 OF 18 DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED | | | RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER | | | AND CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7 | | | ON LAST PAGE OF NOA. NEED THE CALCULATIONS TO MEET THE | | | DESIGN PRESSURES REQUIRED BY SEC. R301.2.1 | | | FBC-RESIDENTIAL. | | | | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|