| Date |
Text |
| 2020-07-21 19:25:20 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE COMPLIANCE WITH FBC EC 405.2.5 FOR EXTERIOR |
| | LIGHTING. LIGHTING MUST BE CONTROLLED BY TIMER SWITCH |
| | CAPABLE OF RETAINING THE HOME TIME SETTING FOR AN EVENT |
| | OF UP TO 10 HOURS AFTER A LOSS OF POWER. A NOTE ON PLAN |
| | WILL SUFFICE. |
| | |
| | 2. REFERENCE PERMIT NUMBER FOR BRANCH CIRCUIT AND |
| | DISCONNECT THAT IS REQUIRED TO POWER SIGN, TO BE DONE |
| | "BY OTHERS" AS ANNOTATED ON PLAN. CIRCUIT MUST BE RAN |
| | BY LICENSED ELECTRICIAN. |
| | |
| | SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C. |
| | 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| | SPECIALTY CONTRACTOR) |
| | |
| | 3.. PLAN IS DIGITALLY SIGNED BUT THERE IS NO 3RD PARTY |
| | VERIFICATION CERTIFICATE FOR DIGITAL SIGNATURE. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |