| 2020-07-20 09:06:16 | PLAN REVIEW ? GENERATOR - DIGITAL SIGNATURES AND SEALS | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | GENERATOR PAD LOAD CALC'S | | | | | | 1) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON | | | ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15 | | | | | | 2) DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | | | 3) UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | | | | | 4) FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY | | | DIGITAL SIGATURES AND SEALS PER FS 668.003. | | | | | | |
|