| Plan Review Notes For Permit 20061426 |
| Permit Number |
20061426 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-20 09:10:11 | PLAN REVIEW ? GENERATOR - ? FUEL GAS | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | PROVIDE GAS RISER DIAGRAHM | | | | | | 1) GAS ISOMETRIC DRAWING: | | | 1A) PROVIDE AN ISO DRAWING SHOWING THE ENTIRE SYSTEM | | | INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST | | | REMOTE OUTLET. THE BTUH LOAD OF EACH APPLIANCE AND THE | | | LOCATIONS OF REGULATORS SHALL BE INDICATED ON THE | | | DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES. | | | 1B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM | | | FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH | | | LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & | | | G2413.4.3. PROVIDED | | | 1B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE | | | OUTLET OF THE REGULATOR- SECTION G2421.1 | | | 1C) PROVIDE THE BTUH LOAD OF THE GENERATOR. G2413.2 FBC | | | RES | | | |
|