Plan Review Notes
Plan Review Notes For Permit 20061417
Permit Number 20061417
Review Stop B
Sequence Number 3
Notes
Date Text
2020-09-28 10:14:48WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061417
 ADD: 700 S. ROSEMARY AVE. UNIT: 140
 CONT: MOCCA CONSTRUCTION
 TEL: 305-964-8440
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. SEPT. 27TH/ 2020
 ACTION: BUILDING PROVISO
  
 1) BUILDING PROVISO: THE STRUCTURAL SHEETS SHOW THE USE
 OF WELDED AND BOLTED CONNECTIONS. THE SHEET S0.0
 STRUCTURAL NOTES REQUIRE SPECIAL INSPECTIONS DONE BY
 3RD PARTY CERTIFICATION, FOR WELDED & BOLTED
 CONNECTIONS. WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 2) BUILDING PROVISO/ DEFERRED SUBMITTAL SHEET
 S0.00SPECIALTY ENGINEERING NOTE G. MECHANICAL TIE-DOWNS
 TO SUPERSTRUCTURE, MECHANICAL SUPPORT CURBS, MECHANICAL
 DUCT SUPPORTS, PIPING SUPPORTS, HANGING EQUIPMENT
 SUPPORTS AND ALL ASSOCIATED CONNECTIONS TO THE
 SUPERSTRUCTURE ARE ALL ASSIGNED TO THE SPECIALTY
 ENGINEER.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
 3) BUILDING PROVISO/ DEFERRED SUBMITTAL: THE ROOF STAND
 NOA: 17-1218.02. / SPECIALTY ENGINEER. 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW. PLEASE PROVIDE THE MIAMI-DADE NOA. THE ROOF TOP
 A/C STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE
 DESIGNER OF RECORD. PLEASE IDENTIFY THE FOLLOWING
 REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE
 ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN
 ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS
 AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND
 THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE
 REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT, FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. 61G1-23.015 (2)
 THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  