| 2020-09-11 17:39:46 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20061417 |
| | ADD: 700 S. ROSEMARY AVE. UNIT: B-17 |
| | CONT: MOCCA CONSTRUCTION |
| | TEL: 305-964-8440 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. SEPT.11/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) BUILDING PROVISO: THE STRUCTURAL SHEETS SHOW THE USE |
| | OF WELDED AND BOLTED CONNECTIONS. THE SHEET S0.0 |
| | STRUCTURAL NOTES REQUIRE SPECIAL INSPECTIONS DONE BY |
| | 3RD PARTY CERTIFICATION, FOR WELDED & BOLTED |
| | CONNECTIONS. WELDED OR BOLTED CONNECTIONS. THE |
| | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT |
| | TIME OF FRAMING INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT |
| | 561-805-6666. |
| | |
| | 2) COMPLIED. MEAN ROOF HEIGHT OF 38.5?. |
| | |
| | 3) SEMI COMPLIED. PRESSURES USING ASCE 7-10 FIGURE |
| | 30-5.1 @ 10 SQ. FT.: |
| | ROOF ZONE 1 +18.27 / -45.4 |
| | ROOF ZONE 2 +18.7 / -76.16 |
| | ROOF ZONE 3 +18.7 / -114.6 |
| | |
| | 1ST ROUND COMMENTS. THE STRUCTURAL SHEET S0.0 PROVIDE A |
| | COMPONENTS AND CLADDING CHART FOR ROOF ZONES 1, 2, & 3. |
| | THE CHART NOR THE WIND DESIGN CRITERIA DOES NOT |
| | INDICATE THE MEAN ROOF HEIGHT, NOR DOES THE COMPONENTS |
| | AND CLADDING CHART INDICATE AT WHAT SQUARE FEET THESE |
| | PRESSURES ARE GIVEN? PRESSURES GIVEN FOR COMPONENTS & |
| | CLADDING FOR ROOFING MATERIALS ARE USUALLY TAKEN FOR 10 |
| | SQUARE FEET, WORST CASE SCENARIO. |
| | |
| | 4) SHEET M7.2 : |
| | 4A) COMPLIED. |
| | |
| | 4B) BUILDING PROVISO/ DEFERRED SUBMITTAL SHEET |
| | S0.00SPECIALTY ENGINEERING NOTE G. MECHANICAL TIE-DOWNS |
| | TO SUPERSTRUCTURE, MECHANICAL SUPPORT CURBS, MECHANICAL |
| | DUCT SUPPORTS, PIPING SUPPORTS, HANGING EQUIPMENT |
| | SUPPORTS AND ALL ASSOCIATED CONNECTIONS TO THE |
| | SUPERSTRUCTURE ARE ALL ASSIGNED TO THE SPECIALTY |
| | ENGINEER. |
| | 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. |
| | |
| | 4C) COMPLIED. |
| | |
| | 4D-F) BUILDING PROVISO/ DEFERRED SUBMITTAL: THE ROOF |
| | STAND NOA: 17-1218.02. / SPECIALTY ENGINEER. |
| | 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. PLEASE PROVIDE THE MIAMI-DADE NOA. |
| | THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| | FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| | OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| | THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| | WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| | ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| | STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| | IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT, FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. 61G1-23.015 (2) |
| | THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| | REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS |
| | ETC.. |
| | |
| | |
| | 5) COMPLIED. |
| | |
| | 6) SHEET A-201 & A-202: |
| | 6A) COMPLIED. |
| | |
| | 6B)COMPLIED, WILL SERVE FREE DRINKING WATER, EXEMPT |
| | FROM 410.4 PLUMB. CODE. |
| | |
| | 7) SEMI-COMPLIED. RESPONSE NOW SHOWS A ACCESSIBLE SEAT |
| | AT THE OUTSIDE BAR, BUT A DETAIL IS NEEDED TO SHOW THE |
| | DROPPED COUNTER TOP IN COMPLIANCE WITH THE 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 902.3 HEIGHT. THE TOPS |
| | OF DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES |
| | MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 1ST ROUND COMMENTS. SHEET G-004/ LA001 SHOWS THE |
| | LOCATION OF THE ACCESSIBLE SEATING ON THE INTERIOR AND |
| | EXTERIOR OF THE BUILDING. IN MOST CASES THE ACCESSIBLE |
| | SEATING MEETS THE ACCESSIBILITY REQUIREMENT OF |
| | DISPERSION OF THE ACCESSIBLE SEATING EXCEPT FOR BAR 003 |
| | SEATING ON THE EXTERIOR PORTION OF THE BAR. |
| | 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 7A) SEMI-COMPLIED. 206.2.5 206.2.5 RESTAURANTS AND |
| | CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN |
| | ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS, |
| | INCLUDING RAISED OR SUNKEN DINING AREAS, AND OUTDOOR |
| | DINING AREAS. |
| | |
| | 7B) SEMI-COMPLIED. 902.1 .DINING SURFACES AND WORK |
| | SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY |
| | 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT |
| | LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. |
| | |
| | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |