Plan Review Notes
Plan Review Notes For Permit 20061417
Permit Number 20061417
Review Stop P
Sequence Number 1
Notes
Date Text
2020-08-18 16:43:4808/18/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. IN SHEET 001 COVER UNDER APPLICABLE CODES PLEASE
 REFER TO THE 6TH EDITION 2017 FBC FUEL GAS CODE PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION.
  
 3. SHEET G-004, G005 AND G-006 ON ADA GUIDELINE;
  
 A. ITEM 1, IT REFERS TO 2014, PLEASE CORRECT AND CHANGE
 TO 2017.
  
 B. ITEM 2, REFERS TO FFPC 5TH EDITION PLEASE CHANGE TO
 THE 6TH EDITION.
  
 C. ITEM 7, SHOULD REFERENCE TEMPERED WATER REQUIRED OF
 110 DEGREES WITH AN ASSE 1070 DEVICE IN ACCORDANCE WITH
 THE 2017 FBC SEC. FBC P 607.1.2.
  
 D. ITEM 10, DOOR HANDLE HARDWARE SHOULD BE NOTED ON
 BOTH SIDES OF THE DOOR PER THE 2017 FBC ACC SEC.
 404.2.7.
  
 E. ITEM 11, SHOULD BE REFERENCED TO 2017 FBC ACC SEC.
 604.4.
  
 F. ITEM 12 AND 13, PLEASE PROVIDE CODE REFERENCE THAT
 APPLIES TO WHAT IS BEING REFERRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 G. ITEM 18, REFERS TO S.F.B.C. PLEASE CHANGE TO 2017
 FBC BUILDING SEC. 1210.2.2.
  
 H. PLEASE NOTE THAT OTHER ITEMS MAY NEED TO BE
 ADDRESSED AS THE LIST IS MANY TO MENTION.
  
 4. SHEET 201 WOMAN'S RESTROOM;
  
 A. IN DETAIL A, THE DOOR IS SWINGING INSIDE THE STALL
 AND IT WILL NEEDS TO SWING OUTWARDS PER THE 2017 FC ACC
 SEC. 608.1.2.
  
 B. IN DETAIL A, THE LAV ON THE OPEN FLOOR NEEDS TO SHOW
 THE CLEAR FLOOR SPACE OF 30" X 48" PER THE 2017 FBC
 SEC. 305.3.
  
 C. IN DETAIL 5, THE HEIGHT OF TOILET OF, MIRROR, GRAB
 BARS AND UNDER LAV ARE MISSING DIMENSIONS PLEASE PROVE
 ACCORDING TO 2017 FBC ACC.
  
 D. IN DETAIL 4, THE TOILET IN THE STALL NEEDS TO BE 17"
 TO 19" INCHES PER 2017 FBC ACC SEC. 604.4.
  
 E. IN DETAIL 4, OPEN FLOOR LAV THE MIRRORS NEED TO AT
 LEAST 40" PER THE 2017 FBC ACC SEC. 603.3.
  
 F. IN DETAIL B, THE REFLECTIVE PART OF THE MIRROR NEEDS
 TO BE THE OF 40" TO THE REFLECTIVE SIDE PER THE 2017
 FBC ACC SEC. 603.3.
  
 G. PLEASE SHOW ALL DIMENSIONS FOR ALL DETAIL OF CLEAR
 FLOOR SPACE ON ALL DETAILS PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. SHEET 202 MEN?S RESTROOM;
  
 A. IN DETAIL A, THE DOOR IS SWINGING INSIDE THE STALL
 AND IT WILL NEEDS TO SWING OUTWARDS PER THE 2017 FC ACC
 SEC. 608.1.
  
 B. IN DETAIL A, THE LAV ON THE OPEN FLOOR NEED TO SHOW
 THE CLEAR FLOOR SPACE OF 30" X 48" PER THE 2017 FBC
 SEC. 305.3.
  
 C. IN DETAIL 2, THE TOILET IN THE STALL NEEDS TO BE 17"
 TO 19" INCHES PER 2017 FBC ACC SEC. 604.4.
  
 D. IN DETAIL 2, AT LEAST ONE OF THE TWO URINALS SHALL
 BE 17" MIN PLEASE SHOW DIMENSION PER THE 2017 FBC ACC.
 SEC. 605.2.
  
 E. IN DETAIL 2, THE REFLECTIVE PART OF THE MIRROR NEEDS
 TO BE THE OF 40" TO THE REFLECTIVE SIDE PER THE 2017
 FBC ACC SEC. 603.3.
  
 F. IN DETAIL 2, SHOW THE HEIGHT FOR ALL PARTITIONS IN
 BETWEEN THE 2017 FBC SEC. P 405.3.5.
  
 G. IN DETAIL 5, THE HEIGHT OF TOILET OF, MIRROR, GRAB
 BARS AND UNDER LAV ARE MISSING DIMENSIONS PLEASE PROVE
 ACCORDING TO 2017 FBC ACC.
  
 6. SHEET 043 P-1;
  
 A. TEMPERED WATER DETAIL FOR LAV IS SAYING WATER AT 105
 DEGREES PLEASE CHANGE TO 110 PER THE 2017 FBC SEC. P
 607.1.2.
  
 B. IN TYPICAL PLUMBING FIXTURES UNDER COFFEE MAKER/ICE
 MAKER REQUIRES AN INLINE VACUUM BREAKER THAT COMPLIES
 WITH THE ASSE 1024 NON-CARBONATED.
  
 C. IN THAT SAME DETAIL, IT CALLS OUT A WASHING MACHINE
 WHICH WILL REQUIRE A LINT TRAP PLEASE SUPPLY DETAILS OR
 NOTE PER THE 2017 FBC SEC. 1003.6.
  
 D. SODA DRINKING BEVERAGE MACHINES SHALL BE PROTECTED
 WITH A DEVICE THAT COMPLIES WITH ASSE 1022 SHALL HAVE
 CARBONATED DISCHARGED TO A SAFE LOCATION PER THE 2017
 FBC SEC. P 608.16.1.
  
 7. SHEET 044 P2-1;
 A. SERVICE SINK (MOP SINK) SURROUNDING WALL SHALL BE IN
 ACCORDANCE WITH A NON-ABSORBENT SURFACE IN ACCORDANCE
 WITH THE 2017 FBC BUILDING SEC. 1210.2.2. PLEASE MAKE A
 NOTE ON THIS SHEET.
  
 8. SHEET 045 P3-1;
  
 A. ON KEYNOTES 1, PLEASE ADD THAT IT SHALL CONFORM ASSE
 1070 ON THE MIXING VALVE.
  
 B. ALL SINKS IN KITCHEN AREA HAVE NOTE 1 ON THEM, THESE
 SINKS REQUIRE HOT WATER AND NEED TO BE NOTED AS SO, NOT
 WITH THE TEMPERED NOTE 1, PLEASE MAKE A NEW NOTE OR
 DELETE NUMBER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. SHEET 044 P2-1;
  
 A. IT SHOWS A GREASE CALCULATION, PLEASE PROVIDE THE
 CAPACITY OF THE EXISTING INTERCEPTOR IN GALLONS.
  
 B. IS IT SHARED WITH OTHER RESTAURANTS AND IF SO, WHAT
 IS THEIR VOLUME.
  
 C. IS IT A PASSIVE HYDROMECHANICAL - OR GRAVITY-TYPE
 GREASE INTERCEPTORS MADE OF CONCRETE STEEL OR
 FIBERGLASS.
  
 D. IN THE KITCHEN AREA THERE IS A THREE-COMPARTMENT
 SINK PLEASE PROVIDE DETAIL ON THE DRAINS TO AN INDIRECT
 WASTE INDEPENDENTLY FORM EACH OTHER PER THE 2017 FBC
 SEC. P 802.1.1.
  
 E. THESE TWO GAS HEATER DISCHARGING CONDENSATION WILL
 NEED A NEUTRALIZING DEVICE THAT WILL BE REQUIRED,
 PLEASE PROVIDE SPECIFICATIONS TO DETERMINE THE PH LEVEL
 PER THE 2017 FBC SEC. P 803.1.
  
 10. PLEASE PROVIDE A DETAIL DRAWING OF THE EMPLOYEE
 ACCESSIBLE RESTROOM IN WITH DIMENSIONS AND HEIGHT
 ELEVATION PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 11. PLEASE SHOW ISOLATION BACKFLOW DEVICE AT ISOMETRIC
 DRAWING AND PUT A NOT ON ITS LOCATION PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  