| 2020-08-18 16:43:48 | 08/18/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB PLUMBING PERMIT IS REQUIRED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 2. IN SHEET 001 COVER UNDER APPLICABLE CODES PLEASE |
| | REFER TO THE 6TH EDITION 2017 FBC FUEL GAS CODE PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION. |
| | |
| | 3. SHEET G-004, G005 AND G-006 ON ADA GUIDELINE; |
| | |
| | A. ITEM 1, IT REFERS TO 2014, PLEASE CORRECT AND CHANGE |
| | TO 2017. |
| | |
| | B. ITEM 2, REFERS TO FFPC 5TH EDITION PLEASE CHANGE TO |
| | THE 6TH EDITION. |
| | |
| | C. ITEM 7, SHOULD REFERENCE TEMPERED WATER REQUIRED OF |
| | 110 DEGREES WITH AN ASSE 1070 DEVICE IN ACCORDANCE WITH |
| | THE 2017 FBC SEC. FBC P 607.1.2. |
| | |
| | D. ITEM 10, DOOR HANDLE HARDWARE SHOULD BE NOTED ON |
| | BOTH SIDES OF THE DOOR PER THE 2017 FBC ACC SEC. |
| | 404.2.7. |
| | |
| | E. ITEM 11, SHOULD BE REFERENCED TO 2017 FBC ACC SEC. |
| | 604.4. |
| | |
| | F. ITEM 12 AND 13, PLEASE PROVIDE CODE REFERENCE THAT |
| | APPLIES TO WHAT IS BEING REFERRED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | G. ITEM 18, REFERS TO S.F.B.C. PLEASE CHANGE TO 2017 |
| | FBC BUILDING SEC. 1210.2.2. |
| | |
| | H. PLEASE NOTE THAT OTHER ITEMS MAY NEED TO BE |
| | ADDRESSED AS THE LIST IS MANY TO MENTION. |
| | |
| | 4. SHEET 201 WOMAN'S RESTROOM; |
| | |
| | A. IN DETAIL A, THE DOOR IS SWINGING INSIDE THE STALL |
| | AND IT WILL NEEDS TO SWING OUTWARDS PER THE 2017 FC ACC |
| | SEC. 608.1.2. |
| | |
| | B. IN DETAIL A, THE LAV ON THE OPEN FLOOR NEEDS TO SHOW |
| | THE CLEAR FLOOR SPACE OF 30" X 48" PER THE 2017 FBC |
| | SEC. 305.3. |
| | |
| | C. IN DETAIL 5, THE HEIGHT OF TOILET OF, MIRROR, GRAB |
| | BARS AND UNDER LAV ARE MISSING DIMENSIONS PLEASE PROVE |
| | ACCORDING TO 2017 FBC ACC. |
| | |
| | D. IN DETAIL 4, THE TOILET IN THE STALL NEEDS TO BE 17" |
| | TO 19" INCHES PER 2017 FBC ACC SEC. 604.4. |
| | |
| | E. IN DETAIL 4, OPEN FLOOR LAV THE MIRRORS NEED TO AT |
| | LEAST 40" PER THE 2017 FBC ACC SEC. 603.3. |
| | |
| | F. IN DETAIL B, THE REFLECTIVE PART OF THE MIRROR NEEDS |
| | TO BE THE OF 40" TO THE REFLECTIVE SIDE PER THE 2017 |
| | FBC ACC SEC. 603.3. |
| | |
| | G. PLEASE SHOW ALL DIMENSIONS FOR ALL DETAIL OF CLEAR |
| | FLOOR SPACE ON ALL DETAILS PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 5. SHEET 202 MEN?S RESTROOM; |
| | |
| | A. IN DETAIL A, THE DOOR IS SWINGING INSIDE THE STALL |
| | AND IT WILL NEEDS TO SWING OUTWARDS PER THE 2017 FC ACC |
| | SEC. 608.1. |
| | |
| | B. IN DETAIL A, THE LAV ON THE OPEN FLOOR NEED TO SHOW |
| | THE CLEAR FLOOR SPACE OF 30" X 48" PER THE 2017 FBC |
| | SEC. 305.3. |
| | |
| | C. IN DETAIL 2, THE TOILET IN THE STALL NEEDS TO BE 17" |
| | TO 19" INCHES PER 2017 FBC ACC SEC. 604.4. |
| | |
| | D. IN DETAIL 2, AT LEAST ONE OF THE TWO URINALS SHALL |
| | BE 17" MIN PLEASE SHOW DIMENSION PER THE 2017 FBC ACC. |
| | SEC. 605.2. |
| | |
| | E. IN DETAIL 2, THE REFLECTIVE PART OF THE MIRROR NEEDS |
| | TO BE THE OF 40" TO THE REFLECTIVE SIDE PER THE 2017 |
| | FBC ACC SEC. 603.3. |
| | |
| | F. IN DETAIL 2, SHOW THE HEIGHT FOR ALL PARTITIONS IN |
| | BETWEEN THE 2017 FBC SEC. P 405.3.5. |
| | |
| | G. IN DETAIL 5, THE HEIGHT OF TOILET OF, MIRROR, GRAB |
| | BARS AND UNDER LAV ARE MISSING DIMENSIONS PLEASE PROVE |
| | ACCORDING TO 2017 FBC ACC. |
| | |
| | 6. SHEET 043 P-1; |
| | |
| | A. TEMPERED WATER DETAIL FOR LAV IS SAYING WATER AT 105 |
| | DEGREES PLEASE CHANGE TO 110 PER THE 2017 FBC SEC. P |
| | 607.1.2. |
| | |
| | B. IN TYPICAL PLUMBING FIXTURES UNDER COFFEE MAKER/ICE |
| | MAKER REQUIRES AN INLINE VACUUM BREAKER THAT COMPLIES |
| | WITH THE ASSE 1024 NON-CARBONATED. |
| | |
| | C. IN THAT SAME DETAIL, IT CALLS OUT A WASHING MACHINE |
| | WHICH WILL REQUIRE A LINT TRAP PLEASE SUPPLY DETAILS OR |
| | NOTE PER THE 2017 FBC SEC. 1003.6. |
| | |
| | D. SODA DRINKING BEVERAGE MACHINES SHALL BE PROTECTED |
| | WITH A DEVICE THAT COMPLIES WITH ASSE 1022 SHALL HAVE |
| | CARBONATED DISCHARGED TO A SAFE LOCATION PER THE 2017 |
| | FBC SEC. P 608.16.1. |
| | |
| | 7. SHEET 044 P2-1; |
| | A. SERVICE SINK (MOP SINK) SURROUNDING WALL SHALL BE IN |
| | ACCORDANCE WITH A NON-ABSORBENT SURFACE IN ACCORDANCE |
| | WITH THE 2017 FBC BUILDING SEC. 1210.2.2. PLEASE MAKE A |
| | NOTE ON THIS SHEET. |
| | |
| | 8. SHEET 045 P3-1; |
| | |
| | A. ON KEYNOTES 1, PLEASE ADD THAT IT SHALL CONFORM ASSE |
| | 1070 ON THE MIXING VALVE. |
| | |
| | B. ALL SINKS IN KITCHEN AREA HAVE NOTE 1 ON THEM, THESE |
| | SINKS REQUIRE HOT WATER AND NEED TO BE NOTED AS SO, NOT |
| | WITH THE TEMPERED NOTE 1, PLEASE MAKE A NEW NOTE OR |
| | DELETE NUMBER PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 9. SHEET 044 P2-1; |
| | |
| | A. IT SHOWS A GREASE CALCULATION, PLEASE PROVIDE THE |
| | CAPACITY OF THE EXISTING INTERCEPTOR IN GALLONS. |
| | |
| | B. IS IT SHARED WITH OTHER RESTAURANTS AND IF SO, WHAT |
| | IS THEIR VOLUME. |
| | |
| | C. IS IT A PASSIVE HYDROMECHANICAL - OR GRAVITY-TYPE |
| | GREASE INTERCEPTORS MADE OF CONCRETE STEEL OR |
| | FIBERGLASS. |
| | |
| | D. IN THE KITCHEN AREA THERE IS A THREE-COMPARTMENT |
| | SINK PLEASE PROVIDE DETAIL ON THE DRAINS TO AN INDIRECT |
| | WASTE INDEPENDENTLY FORM EACH OTHER PER THE 2017 FBC |
| | SEC. P 802.1.1. |
| | |
| | E. THESE TWO GAS HEATER DISCHARGING CONDENSATION WILL |
| | NEED A NEUTRALIZING DEVICE THAT WILL BE REQUIRED, |
| | PLEASE PROVIDE SPECIFICATIONS TO DETERMINE THE PH LEVEL |
| | PER THE 2017 FBC SEC. P 803.1. |
| | |
| | 10. PLEASE PROVIDE A DETAIL DRAWING OF THE EMPLOYEE |
| | ACCESSIBLE RESTROOM IN WITH DIMENSIONS AND HEIGHT |
| | ELEVATION PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 11. PLEASE SHOW ISOLATION BACKFLOW DEVICE AT ISOMETRIC |
| | DRAWING AND PUT A NOT ON ITS LOCATION PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |