| Notes |
| Date |
Text |
| 2020-07-22 10:48:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE DOES NOT APPEAR TO BE A SITE PLAN THAT CLEARLY | | | LOCATES THE PROPOSED TRAILER. | | | | | | PLEASE PROVIDE AN ACCURATE SITE PLAN INCLUDING ALL | | | APPLICABLE DIMENSIONS TO PROPERTY LINES, BUILDING, OR | | | OTHER IMPORTANT SITE FEATURES. | | | | | | | | | | | | 2) THE APPLICATION STATES INSTALL TEMPORARY TRAILER; | | | HOWEVER, THE ATTACHED FOUNDATION PLAN APPEARS TO | | | INDICATE 4 TRAILERS ATTACHED TO EACH OTHER. | | | | | | ADDITIONALLY, THE PREVIOUSLY APPROVED AND ATTACHED FIRE | | | SPRINKLER PERMIT AND THE ELECTRICAL SHOP DRAWINGS | | | INDICATE ONLY ONE TRALIER. | | | | | | PLEASE PROVIDE DETAILED CLARIFICATIONS. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|