| 2020-07-10 15:41:09 | PLAN REVIEW ? FUEL GAS GENERATOR |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | |
| | 1) GAS ISOMETRIC DRAWING: |
| | A) THE DRAWING MUST SHOW THE ENTIRE SYSTEM INCLUDING |
| | ALL BRANCH PIPES FROM THE METER TO THE MOST REMOTE |
| | OUTLET. THE BTUH LOAD OF EACH APPLIANCE AND THE |
| | LOCATIONS OF REGULATORS SHALL BE INDICATED ON THE |
| | DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES. |
| | B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM |
| | FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH |
| | LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & |
| | G2413.4.3. |
| | B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE |
| | OUTLET OF THE REGULATOR- SECTION G2421.1 |
| | C) PROVIDE THE BTUH LOAD OF THE GENERATOR. THE |
| | SUBMITTED SPECS INDICATE 327,000 BTUH FULL LOAD- |
| | G2413.2 FBC RES. |
| | 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH |
| | MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET |
| | AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION |
| | G2421.1. |
| | 3.) SUBMIT SPECS FOR FEX CONNECTORS. SECTION G2421.1. |
| | |
| | |