Plan Review Notes
Plan Review Notes For Permit 20061338
Permit Number 20061338
Review Stop E
Sequence Number 1
Notes
Date Text
2020-07-10 15:47:00PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SHOW GROUNDING ELECTRODE SYSTEM AT SERVICE.
 PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE. NEC 250; FBC RE 3607.3.
 E3607.2 LOCATION OF GROUNDING ELECTRODE CONDUCTOR
 CONNECTION.
  
 2. SHOW CONDUCTOR SIZES AND CABLE TYPE FOR CONTROL
 CIRCUT.
 E3601.4 OTHER CONDUCTORS IN RACEWAY OR CABLE.
 NEC 230.7 & EXHIBIT 230.16
 CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE
 INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE CABLE.
 (230.7)
 EXCEPTIONS:
 1. 1.GROUNDING ELECTRODE CONDUCTORS AND EQUIPMENT
 BONDING JUMPERS OR CONDUCTORS.
 2. 2.LOAD MANAGEMENT CONTROL CONDUCTORS HAVING
 OVERCURRENT PROTECTION.
  
  
  
  