Plan Review Notes For Permit 20061324
Permit Number 20061324
Review Stop B
Sequence Number 2
Notes
Date Text
2020-07-31 14:08:12SHUTTERS -
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW - CORRECTIONS NEEDED - FBC WPB AMENDMENTS
 107
 1) WIND DESIGN PRESSURES ARE BASED ON BUILDING ROOF
 HEIGHT. THIS BUILDING IS A 10 STORY BUILDING.
 2) PLEASE SHOW THE BUILDING ROOF HEIGHT.
 3) PLEASE SHOW THE LOCATION OF THE UNIT WITHIN THE
 BUILDING FOOT PRINT (AN INTERIOR OR END OF BUILDING
 UNIT).- NEEDED TO DETERMINE IF THE WINDOWS ARE IN WIND
 ZONE 4 OR 5.
 4) IF AN END UNIT - PLEASE SHOW THE DISTANCE FROM THE
 CORNER OF THE BUILDING TO THE EDGE OF THE WINDOWS -
 NEEDED TO DETERMINE IF THE WINDOWS ARE IN WIND ZONE 4
 OR 5.
 5) PLEASE SHOW THE LENGTH AND WIDTH OF THE ENTIRE
 BUILDING - NEEDED TO DETERMINE IF THE WINDOWS ARE IN
 WIND ZONE 4 OR 5.
 5) PLEASE PROVIDE SIGNED AND SEALED WIND DESIGN
 PRESSURES FOR THE OPENINGS FROM AN ARCHITECT OR
 ENGINEER - SHOWING THE WIND DESIGN CRITERIA USED FOR
 DESIGN - FBC 1609
 6) PLEASE REVISE THE "SCHEDULE FOR INSTALLATION OF
 OPENINGS" TO REFLECT THE UPDATED WIND DESIGN PRESSURES
 TO BE PROVIDED.