| Plan Review Notes For Permit 20061324 |
| Permit Number |
20061324 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-24 13:14:29 | SHUTTERS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) WIND DESIGN PRESSURES ARE BASED ON BUILDING ROOF | | | HEIGHT. THIS BUILDING IS A 10 STORY BUILDING. | | | 2) PLEASE SHOW THE BUILDING ROOF HEIGHT. | | | 3) PLEASE SHOW THE LOCATION OF THE UNIT WITHIN THE | | | BUILDING FOOT PRINT (AN INTERIOR OR END OF BUILDING | | | UNIT).- NEEDED TO DETERMINE IF THE WINDOWS ARE IN WIND | | | ZONE 4 OR 5. | | | 4) IF AN END UNIT - PLEASE SHOW THE DISTANCE FROM THE | | | CORNER OF THE BUILDING TO THE EDGE OF THE WINDOWS - | | | NEEDED TO DETERMINE IF THE WINDOWS ARE IN WIND ZONE 4 | | | OR 5. | | | 5) PLEASE SHOW THE LENGTH AND WIDTH OF THE ENTIRE | | | BUILDING - NEEDED TO DETERMINE IF THE WINDOWS ARE IN | | | WIND ZONE 4 OR 5. | | | 5) PLEASE PROVIDE SIGNED AND SEALED WIND DESIGN | | | PRESSURES FOR THE OPENINGS FROM AN ARCHITECT OR | | | ENGINEER - SHOW THE WIND DESIGN CRITERIA USED FOR | | | DESIGN - FBC 1609 | | | 6) PLEASE REVISE THE "SCHEDULE FOR INSTALLATION OF | | | OPENINGS" TO REFLECT THE UPDATED WIND DESIGN PRESSURES | | | TO BE PROVIDED. | | | 7) PLEASE SHOW ON THE "SCHEDULE FOR INSTALLATION OF | | | OPENINGS" THE ATTACHMENT ON CENTER SPACING. | | | |
|