| Plan Review Notes For Permit 20061299 |
| Permit Number |
20061299 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-07-14 12:38:40 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) THE RESPONSE LETTER SAYS TILE TO BE "MECHANICALLY | | | ATTACHED" - MECHANICALLY ATTACHED WITH WHAT? - PLEASE | | | SEE ROOFING TILE PRODUCT APPROVAL FOR APPROVED | | | MECHANICAL ATTACHMENTS - AND THEN SHOW ON THE RESPONSE | | | OR CIRCLE THE TYPE OF ATTACHMENT ON THE PRODUCT | | | APPROVAL. PLEASE BE SURE THAT THE ATTACHMENTS MEET THE | | | REQUIRED UPLIFT. | | | |
|