| 2021-04-01 13:26:57 | 6TH REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20061293 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS IS THE 6TH REVIEW ON THIS PROJECT. I HAVE TRIED |
| | TO REACH OUT TO THE ENGINEER ADAM HART BUT HIS |
| | VOICEMAIL IS FULL. I WOULD LIKE TO TALK ABOUT THE |
| | OUTDOOR AIR CALCULATIONS FOR THIS BUILD OUT. PLEASE |
| | CALL ME AS WE MUST HAVE THE INFORMATION REQUESTED IN |
| | ALL OF THE PREVIOUS CYCLES. THE OUTDOOR AIR |
| | CALCULATIONS ARE AN IMPORTANT PART OF THIS DESIGN AND I |
| | MUST SEE THOSE CALCULATIONS BASED ON EACH USE OF SPACE |
| | IN THIS TENANT BUILDOUT. FBC M403.3.1.1 AND TABLE |
| | 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |