Plan Review Notes
Plan Review Notes For Permit 20061293
Permit Number 20061293
Review Stop M
Sequence Number 6
Notes
Date Text
2021-04-01 13:26:576TH REVIEW FBC-2020 MECHANICAL
 PERMIT-20061293
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS THE 6TH REVIEW ON THIS PROJECT. I HAVE TRIED
 TO REACH OUT TO THE ENGINEER ADAM HART BUT HIS
 VOICEMAIL IS FULL. I WOULD LIKE TO TALK ABOUT THE
 OUTDOOR AIR CALCULATIONS FOR THIS BUILD OUT. PLEASE
 CALL ME AS WE MUST HAVE THE INFORMATION REQUESTED IN
 ALL OF THE PREVIOUS CYCLES. THE OUTDOOR AIR
 CALCULATIONS ARE AN IMPORTANT PART OF THIS DESIGN AND I
 MUST SEE THOSE CALCULATIONS BASED ON EACH USE OF SPACE
 IN THIS TENANT BUILDOUT. FBC M403.3.1.1 AND TABLE
 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  