Plan Review Notes
Plan Review Notes For Permit 20061293
Permit Number 20061293
Review Stop P
Sequence Number 5
Notes
Date Text
2021-03-10 13:56:235TH REVIEW FBC-2017 PLUMBING
 PERMIT- 20061293
 3/10/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P0 & P1: THE REVISED PLUMBING PLANS ARE NOT
 MEETING COMPLIANCE WITH SECTION AND TABLE C404.5.1 FBC
 EC. ACCORDING TO THE TABLE THE MAXIMUM ALLOWABLE PIPING
 LENGTH FROM THE NEAREST SOURCE OF HEATED WATER TO THE
 TERMINATION OF THE FIXTURE SUPPLY PIPE AT THE
 LAVATORIES IS 2 FT. FOR 1/2 IN WATER SUPPLY LINES. IT
 APPEARS THAT EITHER A RECIRCULATION PUMP WILL BE
 REQUIRED FOR THE HOT WATER SYSTEM, OR POINT OF USE
 WATER HEATERS MUST BE INSTALLED AT THE LAVATORIES.
 PLEASE NOTE THAT TEMPERED WATER IS ALSO REQUIRED AT THE
 LAVATORIES IN ACCORDANCE WITH SECTIONS 419.5 AND
 607.1.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  