| 2021-03-10 13:56:23 | 5TH REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20061293 |
| | 3/10/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P0 & P1: THE REVISED PLUMBING PLANS ARE NOT |
| | MEETING COMPLIANCE WITH SECTION AND TABLE C404.5.1 FBC |
| | EC. ACCORDING TO THE TABLE THE MAXIMUM ALLOWABLE PIPING |
| | LENGTH FROM THE NEAREST SOURCE OF HEATED WATER TO THE |
| | TERMINATION OF THE FIXTURE SUPPLY PIPE AT THE |
| | LAVATORIES IS 2 FT. FOR 1/2 IN WATER SUPPLY LINES. IT |
| | APPEARS THAT EITHER A RECIRCULATION PUMP WILL BE |
| | REQUIRED FOR THE HOT WATER SYSTEM, OR POINT OF USE |
| | WATER HEATERS MUST BE INSTALLED AT THE LAVATORIES. |
| | PLEASE NOTE THAT TEMPERED WATER IS ALSO REQUIRED AT THE |
| | LAVATORIES IN ACCORDANCE WITH SECTIONS 419.5 AND |
| | 607.1.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |