| 2020-12-29 21:02:20 | 4TH REVIEW FBC-2017 PLUMBING |
| | PERMIT-20061293 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) I DO NOT SEE THE HRCD RESPONSE THAT IS SUPPOSED TO |
| | BE ATTACHED. PLEASE RESPOND TO PREVIOUS REVIEW |
| | COMMENTS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | 2) SHOWER IN RESTROOM A-116 SHALL COMPLY WITH FBC ACC |
| | 213.1, 608.1 |
| | 3) PLAN PAGE P-1 AND A104 INDICATES A DIFFERENT |
| | RESTROOM LAYOUT AND DOES NOT MATCH THE RESTROOMS ON ON |
| | A-3A. PLEASE REMOVE/ REVISE THE PLAN TO SHOW THE |
| | PROPOSED NEW RESTROOM FLOOR PLANS.WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 |
| | 4) PLEASE SHOW ALL INTERIOR RESTROOM DIMENTIONS |
| | REQUIRED FOR A-108. WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 |
| | 5) WATER ISOMETRIC ON P-1 SHALL INDICATE ALL PIPE SIZES |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | 6) COUNTERTOP IN OFFICE A-106 SHALL HAVE A MAX HEIGHT |
| | OF 34" ABOVE FINISHED FLOOR FBC ACC 606.3 |
| | NO FURTHER PLAN REVIEW WILL BE DONE ON THIS PERMIT |
| | APPLICATION UNTIL THE QUALIFIER OF THE COMPANY CONTACTS |
| | THE PLUMBING PLANS EXAMINER AND MEETS WITH THE PLUMBING |
| | PLANS EXAMINER TO REVIEW AND DISCUSS THESE PLAN REVIEW |
| | COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |