2020-12-02 08:39:073RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20061293
 12/2/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST AND 2ND REVIEW PRINTED BELOW
 STILL EXIST. PLEASE NOTE A CORRECTED P1 PLAN SHEET AND
 UPDATED RESPONSE NARRATIVES FROM THE AOR AND EOR WERE
 NOT SUBMITTED. NOTES IN CAPS HAVE BEEN ADDED TO FAILED
 COMMENTS.
  
 1) SHEET P1: REFER TO TABLE 403.3 FBC P AND PROVIDE
 PLUMBING FIXTURE CALCULATIONS FOR THE OCCUPANCY.
 PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES THE
 REQUIRED AND PROVIDED PLUMBING FIXTURES, AND IDENTIFY
 THE LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS AND
 SERVICE SINK ON THE FLOOR PLAN. NOT PROVIDED. THE
 ARCHITECT AND ENGINEER OF RECORD SHALL PLEASE PROVIDE
 THE CALCULATIONS AND ADD INSTALLATION OF PRIVATE
 RESTROOMS TO THE SCOPE OF WORK FOR THE PROJECT.
  
 2) P1: PLEASE LABEL THE NEW TOILET ROOMS AS EITHER MALE
 OR FEMALE- SECTION 403.2. NOT PROVIDED- SEE COMMENT #1.
  
 3) P1: THE 4" SANITARY DRAIN FROM RR A-104 CANNOT MAKE
 CONNECTION INTO THE 3" SANITARY DRAIN SERVING OFFICE
 AND RR A-106 BECAUSE DRAINAGE PIPES CANNOT BE REDUCED
 IN SIZE IN THE DIRECTION OF FLOW- SECTION 704.2. NO
 CHANGES WERE MADE TO THE PLUMBING PLAN- PLANS REMAIN
 NON-COMPLIANT.
  
 4) P1: INDICATE THE SIZE OF THE SINK DRAIN FROM OFFICE
 A-106. PLEASE NOTE THAT THE DRAIN MUST MAKE CONNECTION
 TO THE MAIN DRAIN AT A POINT DOWNSTREAM OF THE WATER
 CLOSET IN ORDER FOR THE WET VENT IN RR-106 TO BE IN
 COMPLIANCE WITH SECTION 912.1. NO CHANGES WERE MADE TO
 THE PLUMBING PLANS- THE PLAN DEPICTS A NON-COMPLIANT
 HORIZONTAL WET VENT FOR THE RESTROOM A-108.
  
 5) P1: A NEW BACKFLOW PREVENTER IS SHOWN ON THE WATER
 RISER PLEASE NOTE A SEPARATE PERMIT IS REQUIRED-
 SECTION 107.2.1. PLEASE NOTE THAT A FL. LICENSED
 PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC, 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 6) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORIES- SECTION 416.5 FBC P. NO CHANGES WERE
 MADE TO THE PLUMBING PLANS- PLANS REMAIN NON-COMPLIANT.
  
 7) P1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE-
 SECTION 107.2.1 WPB & SECTION 405.9 FBC P. NO CHANGES
 WERE MADE TO THE PLUMBING PLANS- PLANS REMAIN
 NON-COMPLIANT.
  
 9) A3: ITEMS A, B, C, D, I NON-COMPLIANT.
  
 A) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE WATER CLOSETS- SECTION 604.3. DIMENSIONS OF
 CLEAR FLOOR SPACES NOT SHOWN.
  
 B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE LAVATORIES- SECTION 606.2. DIMENSIONS OF CLEAR
 FLOOR SPACES NOT SHOWN.
  
 C) FAILED. ENTRY DOOR WIDTHS, DOOR SWING, AND
 WHEELCHAIR APPROACHES. PLEASE NOTE THAT DOOR A-10 SHALL
 NOT SWING INTO REQUIRED CLEAR FLOOR SPACES FOR THE
 LAVATORY. PLEASE SEE SECTION 603.2.3 EXCEPTIONS #1 & #2
 AND SHOW COMPLIANCE.
  
 D) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3.
 DIAMETERS NOT PROVIDED.
  
 I) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS- SECTION 604.5 & 609.4. GRAB BAR HEIGHTS ARE
 MEASURED FROM THE FINISHED FLOORS TO THE TOP OF THE
 GRIPPING SURFACES.
  
 J) FAILED. LOCATION OF THE WATER CLOSET FLUSH CONTROLS-
 SECTION 604.6. NOT PROVIDED.
 L) FAILED. HEIGHTS OF THE MIRROR FROM THE FINISHED
 FLOORS TO THE BOTTOMS OF THE REFLECTIVE SURFACES-
 SECTION 603.3. THE DRAWING SHOWS THE MEASUREMENT TO THE
 BOTTOM OF THE FRAME NOT THE REFLECTIVE SURFACE.
  
 10) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
 NOT PROVIDED.
  
 NEW COMMENTS.
  
 11) SHEET P1: PLEASE PROVIDE A PLUMBING RISER DRAWING
 FOR THE NEW HI-LO DRINKING FOUNTAIN- SECTION
 107.3.5.1.3 WPB.
  
 12) A3 & A5: REFER TO BUILDING REVIEW COMMENT #1A
 CONCERNING THE NEW LAVATORY CABINET IN THE ADA
 RESTROOM. IN ADDITON PLEASE PROVIDE THE DIMENSIONS OF
 THE CLEAR FLOOR SPACE DIAGRAMS FPOR THE WATER CLOSET
 AND LAVATORY, AND TURNING CIRCLE DIAMETER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  