Plan Review Notes
Plan Review Notes For Permit 20061293
Permit Number 20061293
Review Stop M
Sequence Number 3
Notes
Date Text
2021-03-05 13:58:43 
  
2020-12-02 14:01:53PLAN DENIED
 1) DUCT SIZE REQUIRED
 OFFICE ROOM A - 106 RETURN AIR DUCT
 OFFICE ROOM A - 101 RETURN AIR AND SUPPLY DUCT
 CONTROL ROOM A - 105 RETURN AIR DUCT
 SECTION 107 FBC 2017
 2) PROVIDE MODEL NUMBER OF AIR CONDITIONING UNIT
 ON EQUIPMENT SCHEDULE SECTION 107 FBC 2017
 3) REFER TO SECTION 606.2.1 FBC(M) AND PROVIDE
 MANUFACTURES
 INSTALLATION INSTRUCTIONS FOR AIR CONDITIONING UNIT AT
 FIRST INSPECTION.
 4) PROVIDE CFM ON BATHROOM EXHAUST FAN SCHEDULE PER
 TABLE
 403.3.1.1 FBC(M)
 5) PROVIDE FRESH AIR CALCULATIONS ON PLAN.
 PER TABLE 403.3.1.1 FBC(M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  