| Plan Review Notes For Permit 20061293 |
| Permit Number |
20061293 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-03-05 13:58:43 | | | | | | 2020-12-02 14:01:53 | PLAN DENIED | | | 1) DUCT SIZE REQUIRED | | | OFFICE ROOM A - 106 RETURN AIR DUCT | | | OFFICE ROOM A - 101 RETURN AIR AND SUPPLY DUCT | | | CONTROL ROOM A - 105 RETURN AIR DUCT | | | SECTION 107 FBC 2017 | | | 2) PROVIDE MODEL NUMBER OF AIR CONDITIONING UNIT | | | ON EQUIPMENT SCHEDULE SECTION 107 FBC 2017 | | | 3) REFER TO SECTION 606.2.1 FBC(M) AND PROVIDE | | | MANUFACTURES | | | INSTALLATION INSTRUCTIONS FOR AIR CONDITIONING UNIT AT | | | FIRST INSPECTION. | | | 4) PROVIDE CFM ON BATHROOM EXHAUST FAN SCHEDULE PER | | | TABLE | | | 403.3.1.1 FBC(M) | | | 5) PROVIDE FRESH AIR CALCULATIONS ON PLAN. | | | PER TABLE 403.3.1.1 FBC(M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | | | | |
|