Plan Review Notes
Plan Review Notes For Permit 20061293
Permit Number 20061293
Review Stop P
Sequence Number 2
Notes
Date Text
2020-10-15 14:58:532ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20061293
 10/15/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT
 ADDRESSED. PLEASE NOTE THE CORRECTED P1 PLAN AND THE
 RESPONSE NARRATIVE FROM THE ENGINEER OF RECORD- HRCD
 WERE NOT SUBMITTED. PLEASE SEE ADDITIONAL NOTES IN CAP
 LETTERS UNDER COMMENT 9.
  
 1) SHEET P1: REFER TO TABLE 403.3 FBC P AND PROVIDE
 PLUMBING FIXTURE CALCULATIONS FOR THE OCCUPANCY.
 PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES THE
 REQUIRED AND PROVIDED PLUMBING FIXTURES, AND IDENTIFY
 THE LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS AND
 SERVICE SINK ON THE FLOOR PLAN.
  
 2) P1: PLEASE LABEL THE NEW TOILET ROOMS AS EITHER MALE
 OR FEMALE- SECTION 403.2.
  
 3) P1: THE 4" SANITARY DRAIN FROM RR A-104 CANNOT MAKE
 CONNECTION INTO THE 3" SANITARY DRAIN SERVING OFFICE
 AND RR A-106 BECAUSE DRAINAGE PIPES CANNOT BE REDUCED
 IN SIZE IN THE DIRECTION OF FLOW- SECTION 704.2.
  
 4) P1: INDICATE THE SIZE OF THE SINK DRAIN FROM OFFICE
 A-106. PLEASE NOTE THAT THE DRAIN MUST MAKE CONNECTION
 TO THE MAIN DRAIN AT A POINT DOWNSTREAM OF THE WATER
 CLOSET IN ORDER FOR THE WET VENT IN RR-106 TO BE IN
 COMPLIANCE WITH SECTION 912.1.
  
 5) P1: A NEW BACKFLOW PREVENTER IS SHOWN ON THE WATER
 RISER PLEASE NOTE A SEPARATE PERMIT IS REQUIRED-
 SECTION 107.2.1. PLEASE NOTE THAT A FL. LICENSED
 PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC, 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 6) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORIES- SECTION 416.5 FBC P.
  
 7) P1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE-
 SECTION 107.2.1 WPB & SECTION 405.9 FBC P.
  
 8) SHEET A1: PLEASE UPDATE THE 2012 FL. ACCESSIBILITY
 CODE REFERENCE TO THE 2017 SIXTH EDITION.
  
 9) A3 & P1: THE NEW TOILETS ROOMS SHALL BE DESIGNED IN
 ACCORDANCE WITH THE FLORIDA ACCESSIBILITY CODE- 2017
 SIXTH EDITION. REFER TO SECTION 213 AND PROVIDE
 ENLARGED, DIMENSIONED TOILET ROOM DRAWINGS SHOWING: THE
 REQUESTED ENLARGED DRAWINGS WERE NOT PROVIDED. COMMENTS
 (A- L ) ARE MARKED PASSED, FAILED, OR NOT REQUIRED.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE WATER CLOSETS- SECTION 604.3.
 B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE LAVATORIES- SECTION 606.2.
 C) FAILED. ENTRY DOOR WIDTHS, DOOR SWING, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3.
 PLEASE NOTE THAT DOORS SHALL NOT SWING INTO REQUIRED
 CLEAR FLOOR SPACES FOR FIXTURES. DOOR A-10 MUST BE
 REVERSABLE.
 D) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3.
 E) PASSED. CENTERLINES OF THE WATER CLOSETS FROM THE
 SIDE WALL- SECTION 604.2.
 F) NOT REQUIRED FOR PRIVATE TOILET FOOMS. HEIGHTS OF
 THE WATER CLOSET SEATS FROM THE FINISHED FLOORS-
 SECTION 604.4.
 G) NOT REQUIRED FOR PRIVATE TOILET ROOMS. HEIGHTS OF
 THE FRONT RIM OF THE LAVATORIES FROM THE FINISHED
 FLOORS- SECTION 606.3
 H) NOT REQUIRED FOR PRIVATE TOILET ROOMS. KNEE AND TOE
 CLEARANCES FOR THE LAVATORIES- SECTION 306.
 I) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS- SECTION 604.5 & 609.4
 J) FAILED. LOCATION OF THE WATER CLOSET FLUSH CONTROLS-
 SECTION 604.6.
 K) FAILED. LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS
 FOR THE TOILET PAPER DISPENSERS- SECTION 604.7.
 L) FAILED. HEIGHTS OF THE MIRROR FROM THE FINISHED
 FLOORS TO THE BOTTOMS OF THE REFLECTIVE SURFACES-
 SECTION 603.3.
  
 10) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 11) PROVIDE FINISH MATERIAL SCHEDULES FOR THE TOILET
 ROOM FLOORS AND WALLS- SECTION 310.3 FBC P AND SECTION
 1210.2.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  