| 2020-10-15 14:58:53 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20061293 |
| | 10/15/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT |
| | ADDRESSED. PLEASE NOTE THE CORRECTED P1 PLAN AND THE |
| | RESPONSE NARRATIVE FROM THE ENGINEER OF RECORD- HRCD |
| | WERE NOT SUBMITTED. PLEASE SEE ADDITIONAL NOTES IN CAP |
| | LETTERS UNDER COMMENT 9. |
| | |
| | 1) SHEET P1: REFER TO TABLE 403.3 FBC P AND PROVIDE |
| | PLUMBING FIXTURE CALCULATIONS FOR THE OCCUPANCY. |
| | PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES THE |
| | REQUIRED AND PROVIDED PLUMBING FIXTURES, AND IDENTIFY |
| | THE LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS AND |
| | SERVICE SINK ON THE FLOOR PLAN. |
| | |
| | 2) P1: PLEASE LABEL THE NEW TOILET ROOMS AS EITHER MALE |
| | OR FEMALE- SECTION 403.2. |
| | |
| | 3) P1: THE 4" SANITARY DRAIN FROM RR A-104 CANNOT MAKE |
| | CONNECTION INTO THE 3" SANITARY DRAIN SERVING OFFICE |
| | AND RR A-106 BECAUSE DRAINAGE PIPES CANNOT BE REDUCED |
| | IN SIZE IN THE DIRECTION OF FLOW- SECTION 704.2. |
| | |
| | 4) P1: INDICATE THE SIZE OF THE SINK DRAIN FROM OFFICE |
| | A-106. PLEASE NOTE THAT THE DRAIN MUST MAKE CONNECTION |
| | TO THE MAIN DRAIN AT A POINT DOWNSTREAM OF THE WATER |
| | CLOSET IN ORDER FOR THE WET VENT IN RR-106 TO BE IN |
| | COMPLIANCE WITH SECTION 912.1. |
| | |
| | 5) P1: A NEW BACKFLOW PREVENTER IS SHOWN ON THE WATER |
| | RISER PLEASE NOTE A SEPARATE PERMIT IS REQUIRED- |
| | SECTION 107.2.1. PLEASE NOTE THAT A FL. LICENSED |
| | PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| | INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| | WITH SECTION 105.1 WPB AND SEC, 90-33 WPB CODE OF |
| | ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| | THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| | BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| | UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| | FURTHER INFORMATION. |
| | |
| | 6) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO |
| | THE LAVATORIES- SECTION 416.5 FBC P. |
| | |
| | 7) P1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE- |
| | SECTION 107.2.1 WPB & SECTION 405.9 FBC P. |
| | |
| | 8) SHEET A1: PLEASE UPDATE THE 2012 FL. ACCESSIBILITY |
| | CODE REFERENCE TO THE 2017 SIXTH EDITION. |
| | |
| | 9) A3 & P1: THE NEW TOILETS ROOMS SHALL BE DESIGNED IN |
| | ACCORDANCE WITH THE FLORIDA ACCESSIBILITY CODE- 2017 |
| | SIXTH EDITION. REFER TO SECTION 213 AND PROVIDE |
| | ENLARGED, DIMENSIONED TOILET ROOM DRAWINGS SHOWING: THE |
| | REQUESTED ENLARGED DRAWINGS WERE NOT PROVIDED. COMMENTS |
| | (A- L ) ARE MARKED PASSED, FAILED, OR NOT REQUIRED. |
| | A) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS |
| | FOR THE WATER CLOSETS- SECTION 604.3. |
| | B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS |
| | FOR THE LAVATORIES- SECTION 606.2. |
| | C) FAILED. ENTRY DOOR WIDTHS, DOOR SWING, AND |
| | WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3. |
| | PLEASE NOTE THAT DOORS SHALL NOT SWING INTO REQUIRED |
| | CLEAR FLOOR SPACES FOR FIXTURES. DOOR A-10 MUST BE |
| | REVERSABLE. |
| | D) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3. |
| | E) PASSED. CENTERLINES OF THE WATER CLOSETS FROM THE |
| | SIDE WALL- SECTION 604.2. |
| | F) NOT REQUIRED FOR PRIVATE TOILET FOOMS. HEIGHTS OF |
| | THE WATER CLOSET SEATS FROM THE FINISHED FLOORS- |
| | SECTION 604.4. |
| | G) NOT REQUIRED FOR PRIVATE TOILET ROOMS. HEIGHTS OF |
| | THE FRONT RIM OF THE LAVATORIES FROM THE FINISHED |
| | FLOORS- SECTION 606.3 |
| | H) NOT REQUIRED FOR PRIVATE TOILET ROOMS. KNEE AND TOE |
| | CLEARANCES FOR THE LAVATORIES- SECTION 306. |
| | I) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS- SECTION 604.5 & 609.4 |
| | J) FAILED. LOCATION OF THE WATER CLOSET FLUSH CONTROLS- |
| | SECTION 604.6. |
| | K) FAILED. LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS |
| | FOR THE TOILET PAPER DISPENSERS- SECTION 604.7. |
| | L) FAILED. HEIGHTS OF THE MIRROR FROM THE FINISHED |
| | FLOORS TO THE BOTTOMS OF THE REFLECTIVE SURFACES- |
| | SECTION 603.3. |
| | |
| | 10) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB. |
| | |
| | 11) PROVIDE FINISH MATERIAL SCHEDULES FOR THE TOILET |
| | ROOM FLOORS AND WALLS- SECTION 310.3 FBC P AND SECTION |
| | 1210.2.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |