Plan Review Notes
Plan Review Notes For Permit 20061293
Permit Number 20061293
Review Stop B
Sequence Number 2
Notes
Date Text
2020-10-16 16:20:20WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061293
 ADD: 3 HARVARD CIR.
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-646-0412
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. OCT.16TH/ 2020
 ACTION: DENIED
  
 1) SEMI-COMPLIED/ DISPROPORTIONATE COST 202.4.1. THERE
 ARE STILL A FEW ACCESSIBILITY ISSUES WITH THE RESTROOMS
 SEE BELOW COMMENTS.
  
 1A) SHEET A-3. SEMI-COMPLIED. VERSION ONE OF THE PLANS
 INDICATES THE EXISTING EXECUTIVE RESTROOM. VERSION 2
 NOW STATES THAT THE CONVERTED EXECUTIVE RESTROOM IS AN
 EXISTING ADA RESTROOM, WHERE THE RESTROOM IN QUESTION
 IS THE 2ND REQUIRED ADA RESTROOM COMPLYING WITH
 FBC-ACCESSIBILITY SECTION 213.2EXCEPTION 4. CORRECT
 NAME TO NEW ADA RESTROOM.
 1A)(1) NEW COMMENT. THE NEW PROPOSED ADA RESTROOM THE
 DETAIL DOES STATE (1) TO REMOVE THE EXISTING VERTICAL
 CABINET AND (2) RECONFIGURE EXISTING CABINET/ SINK PER
 REQUIRED ADA REQUIREMENTS SEE SHEET A-5. SHEET A-5 DOES
 SHOW ACCESSIBLE DETAILS BUT THERE IS NO OVERALL FLOOR
 PLAN DETAIL SHOWING THE SIZE OF THE CABINET WITH CLEAR
 FLOOR SPACE. SHEET A-3 SHOWS CABINETRY THAT NEEDS TO BE
 REMOVED TO SHOW CODE COMPLIANCE FOR THE REQUIRED CLEAR
 FLOOR SPACE FOR THE WATER CLOSET
 (CLEARANCES AT WATER CLOSETS. 604.3.1 CLEARANCE) AND
 MANEUVERING CLEARANCES OF 18 INCHES LATCH SIDE OF THE
 DOOR (ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 DOORS.)
  
 1B) SHEET A-3. COMPLIED. SHEET A-3 COMPLIES HIGH/ LOW
 DRINKING FOUNTAIN.
  
 1C) NEW COMMENT. SHEET A-5 NOW SHOWS NEW ACCESSIBLE
 RESTROOM ELEMENT DETAILS, PLEASE NOTE THE GRAB BAR
 DETAILS ARE MEASURED FROM FINISH FLOOR TO CENTERLINE OF
 THE GRAB BAR. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4
 POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 1D) NEW COMMENT DEALS WITH THE RESTROOMS THAT ARE BEING
 RECONFIGURED WILL NEED TO SHOW COMPLIANCE WITH: 2017
 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A
 RESULT OF THE BUILDING OFFICIAL INTERPRETATION. IN
 RESTROOMS EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH
 HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
 2017 FBC-B 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET
 WALLS SHALL COMPLY WITH 1210.2.
 2017 FBC-B 1210.2. FINISH MATERIALS. WALLS, BASE,
 FLOORS AND PARTITIONS IN TOILET AND BATHROOMS SHALL
 COMPLY WITH SECTIONS 1210.1 THROUGH 1210.4.
  
 2) BUILDING PROVISO/ DEFERRED SUBMITTALS. SHEET A-3 &
 S-1 BOTH SHOW NEW EXTERIOR DOOR OPENING. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS,
  
 2A) BUILDING PROVISO / DEFERRED SUBMITTAL.W. P. B.
 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE 61G20
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2B) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  