| 2020-08-14 07:28:11 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20061293 |
| | 8/13/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: REFER TO TABLE 403.3 FBC P AND PROVIDE |
| | PLUMBING FIXTURE CALCULATIONS FOR THE OCCUPANCY. |
| | PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES THE |
| | REQUIRED AND PROVIDED PLUMBING FIXTURES, AND IDENTIFY |
| | THE LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS AND |
| | SERVICE SINK ON THE FLOOR PLAN. |
| | |
| | 2) P1: PLEASE LABEL THE NEW TOILET ROOMS AS EITHER MALE |
| | OR FEMALE- SECTION 403.2. |
| | |
| | 3) P1: THE 4" SANITARY DRAIN FROM RR A-104 CANNOT MAKE |
| | CONNECTION INTO THE 3" SANITARY DRAIN SERVING OFFICE |
| | AND RR A-106 BECAUSE DRAINAGE PIPES CANNOT BE REDUCED |
| | IN SIZE IN THE DIRECTION OF FLOW- SECTION 704.2. |
| | |
| | 4) P1: INDICATE THE SIZE OF THE SINK DRAIN FROM OFFICE |
| | A-106. PLEASE NOTE THAT THE DRAIN MUST MAKE CONNECTION |
| | TO THE MAIN DRAIN AT A POINT DOWNSTREAM OF THE WATER |
| | CLOSET IN ORDER FOR THE WET VENT IN RR-106 TO BE IN |
| | COMPLIANCE WITH SECTION 912.1. |
| | |
| | 5) P1: A NEW BACKFLOW PREVENTER IS SHOWN ON THE WATER |
| | RISER PLEASE NOTE A SEPARATE PERMIT IS REQUIRED- |
| | SECTION 107.2.1. PLEASE NOTE THAT A FL. LICENSED |
| | PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| | INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| | WITH SECTION 105.1 WPB AND SEC, 90-33 WPB CODE OF |
| | ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| | THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| | BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| | UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| | FURTHER INFORMATION. |
| | |
| | 6) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO |
| | THE LAVATORIES- SECTION 416.5 FBC P. |
| | |
| | 7) P1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE- |
| | SECTION 107.2.1 WPB & SECTION 405.9 FBC P. |
| | |
| | 8) SHEET A1: PLEASE UPDATE THE 2012 FL. ACCESSIBILITY |
| | CODE REFERENCE TO THE 2017 SIXTH EDITION. |
| | |
| | 9) A3 & P1: THE NEW TOILETS ROOMS SHALL BE DESIGNED IN |
| | ACCORDANCE WITH THE FLORIDA ACCESSIBILITY CODE- 2017 |
| | SIXTH EDITION. REFER TO SECTION 213 AND PROVIDE |
| | ENLARGED, DIMENSIONED TOILET ROOM DRAWINGS SHOWING: |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | C) ENTRY DOOR WIDTHS, DOOR SWING, AND WHEELCHAIR |
| | APPROACHES- SECTION 604.8.1.2 & 604.8.1.3. PLEASE NOTE |
| | THAT DOORS SHALL NOT SWING INTO REQUIRED CLEAR FLOOR |
| | SPACES FOR FIXTURES. |
| | D) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | E) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALL- |
| | SECTION 604.2. |
| | F) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | G) HEIGHTS OF THE FRONT RIM OF THE LAVATORIES FROM THE |
| | FINISHED FLOORS- SECTION 606.3 |
| | H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 306. |
| | I) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECTION 604.5 & 609.4 |
| | J) LOCATION OF THE WATER CLOSET FLUSH CONTROLS- SECTION |
| | 604.6. |
| | K) LOCATION, CLEARANCE, AND MOUNTING HEIGHTS FOR THE |
| | TOILET PAPER DISPENSERS- SECTION 604.7. |
| | L) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOORS TO |
| | THE BOTTOMS OF THE REFLECTIVE SURFACES- SECTION 603.3. |
| | |
| | 10) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB. |
| | |
| | 11) PROVIDE FINISH MATERIAL SCHEDULES FOR THE TOILET |
| | ROOM FLOORS AND WALLS- SECTION 310.3 FBC P AND SECTION |
| | 1210.2.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |