| Plan Review Notes For Permit 20061293 |
| Permit Number |
20061293 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-16 14:48:29 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) COVER & A 3 SHEETS - THERE ARE REFERENCES TO | | | INCORRECT EDITION OF THE FIRE CODE. | | | | | | THE PROPOSED PROJECT SHALL COMPLY WITH THE CURRENT | | | ADOPTED EDITION OF THE FLORIDA FIRE PREVENTION CODE | | | WHICH INCLUDES THE 2015 EDITIONS OF NFPA 1 & 101. | | | | | | PLEASE REVIEW THOSE EDITIONS AND ENSURE COMPLIANCE WITH | | | THE PROPOSED. | | | | | | PLEASE CORRECT TO THE CURRENT ADOPTED EDITIONS. | | | | | | | | | 2) SHEET E 2 - THERE ARE INDICATIONS OF FIRE ALARM | | | DEVICES. | | | | | | ANY WORK OF THE FIRE ALARM SYSTEM SHALL BE DONE UNDER | | | SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | | ACKNOWLEDGEMENT. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|