Plan Review Notes
Plan Review Notes For Permit 20061293
Permit Number 20061293
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-07-16 14:48:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) COVER & A 3 SHEETS - THERE ARE REFERENCES TO
 INCORRECT EDITION OF THE FIRE CODE.
  
 THE PROPOSED PROJECT SHALL COMPLY WITH THE CURRENT
 ADOPTED EDITION OF THE FLORIDA FIRE PREVENTION CODE
 WHICH INCLUDES THE 2015 EDITIONS OF NFPA 1 & 101.
  
 PLEASE REVIEW THOSE EDITIONS AND ENSURE COMPLIANCE WITH
 THE PROPOSED.
  
 PLEASE CORRECT TO THE CURRENT ADOPTED EDITIONS.
  
  
 2) SHEET E 2 - THERE ARE INDICATIONS OF FIRE ALARM
 DEVICES.
  
 ANY WORK OF THE FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  