2020-08-19 22:15:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FIRE ALARM MUST BE SUBMITTED UNDER A SEPARATE PERMIT
 WITH SEPARATE PLANS. FBC 107.2.1 FBC 105.1
  
 2. LOW VOLTAGE MUST ALSO BE A SEPARATE PERMIT BUT A LOW
 VOLTAGE REVIEW STOP CAN BE ADDED TO MASTER PERMIT FOR
 REVIEW. PLEASE REMOVE ALL FIRE ALARM FROM LV DRAWINGS.
 FBC 107.2.1 FBC 105.1
  
 3. IS RISER DIAGRAM PROVIDED EXISTING OR PROPOSED? NO
 OCP SHOWN FOR MAINS ON RISER DIAGRAM. FBC 107.2.1
  
 4. NO EQUIPMENT GROUNDS SHOWN FOR PANELS "H" AND "A"ON
 RISER DIAGRAM?
  
 5. NO HVAC LOAD SHOWN IN LOAD CALC?
  
 6. LIGHTING MUST BE CALCULATED AT 125% IN LOAD CALC FOR
 CONTINUOUS LOADS NEC 210.19A
  
 7. VA PER SQ/FT FOR OFFICE BUILDINGS IS 3.5VA NOT 2VA
 WHICH IS WHAT IS IN LOAD CALC NOW. NEC 220.12
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved