| Date |
Text |
| 2020-07-20 13:44:04 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20061293 |
| | ADD: 3 HARVARD CIR. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 954-646-0412 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 20TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES THE PERMIT VALUE |
| | FOR THIS PROJECT IS $250,000.00 DOLLARS. EXISTING BLDG. |
| | CODE- ACCESSIBILITY. UNDER THE 2017 EXISTING BUILDING |
| | CODE LEVEL II ALTERATIONS, SECTION 806.1 A BUILDING, |
| | FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH |
| | THE PROVISIONS OF THE FLORIDA BUILDING CODE- |
| | ACCESSIBILITY. IN THE ACCESSIBILITY CODE IT REFERS YOU |
| | TO DISPROPORTIONATE |
| | |
| | DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU |
| | ARE TO MEET DISPROPORTIONATE COST. EITHER THE |
| | CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR |
| | LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP |
| | TO THE 20% ($50,000.00) DISPROPORTIONATE FUNDS LISTED |
| | FOR EACH ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN |
| | THE ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE |
| | COST OF THE 2017 ACCESSIBILITY CODE. |
| | |
| | 1A) SHEET A-3. PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY |
| | CODE SECTION 213.2 EXCEPTION 4. WHERE MULTIPLE SINGLE |
| | TOILET ROOMS ARE CLUSTERED AT A SINGLE LOCATION, NO |
| | MORE THAN 50 PERCENT OF THE SINGLE TOILET ROOMS FOR USE |
| | AT EACH CLUSTER SHALL BE REQUIRED TO COMPLY WITH 603. |
| | ADVISORY. A CLUSTER IS A GROUP OF TOILET ROOMS |
| | PROXIMATE TO ONE ANOTHER. GENERALLY TOILET ROOMS IN A |
| | CLUSTER ARE WITHIN SIGHT OF ONE ANOTHER, OR ADJACENT |
| | TO, ONE ANOTHER. |
| | |
| | 1B) SHEET A-3. SHEET A-3 SHOWS A SINGLE USE WATER |
| | FOUNTAIN NOT A HIGH/ LOW DRINKING FOUNTAIN. PLEASE SHOW |
| | COMPLIANCE WITH: |
| | DRINKING FOUNTAINS. |
| | 1B)(1) 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM |
| | NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE |
| | PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 |
| | THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY |
| | WITH 602.7. |
| | |
| | 1B)(2) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS |
| | 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES |
| | AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT |
| | PROTRUDE MORE THAN 4 INCHES HORIZONTALLY IN TO THE |
| | CIRCULATION PATH. |
| | |
| | 1B)(3) 60.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED. |
| | |
| | 2) SHEET A-3 & S-1 BOTH SHOW NEW EXTERIOR DOOR OPENING. |
| | PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, |
| | |
| | 2A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2B) IDENTIFY GLAZING/ MULLIONS. |
| | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |