Plan Review Notes
Plan Review Notes For Permit 20061293
Permit Number 20061293
Review Stop B
Sequence Number 1
Notes
Date Text
2020-07-20 13:44:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061293
 ADD: 3 HARVARD CIR.
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-646-0412
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 20TH/ 2020
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE PERMIT VALUE
 FOR THIS PROJECT IS $250,000.00 DOLLARS. EXISTING BLDG.
 CODE- ACCESSIBILITY. UNDER THE 2017 EXISTING BUILDING
 CODE LEVEL II ALTERATIONS, SECTION 806.1 A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE-
 ACCESSIBILITY. IN THE ACCESSIBILITY CODE IT REFERS YOU
 TO DISPROPORTIONATE
  
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% ($50,000.00) DISPROPORTIONATE FUNDS LISTED
 FOR EACH ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN
 THE ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE
 COST OF THE 2017 ACCESSIBILITY CODE.
  
 1A) SHEET A-3. PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY
 CODE SECTION 213.2 EXCEPTION 4. WHERE MULTIPLE SINGLE
 TOILET ROOMS ARE CLUSTERED AT A SINGLE LOCATION, NO
 MORE THAN 50 PERCENT OF THE SINGLE TOILET ROOMS FOR USE
 AT EACH CLUSTER SHALL BE REQUIRED TO COMPLY WITH 603.
 ADVISORY. A CLUSTER IS A GROUP OF TOILET ROOMS
 PROXIMATE TO ONE ANOTHER. GENERALLY TOILET ROOMS IN A
 CLUSTER ARE WITHIN SIGHT OF ONE ANOTHER, OR ADJACENT
 TO, ONE ANOTHER.
  
 1B) SHEET A-3. SHEET A-3 SHOWS A SINGLE USE WATER
 FOUNTAIN NOT A HIGH/ LOW DRINKING FOUNTAIN. PLEASE SHOW
 COMPLIANCE WITH:
 DRINKING FOUNTAINS.
 1B)(1) 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
  
 1B)(2) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY IN TO THE
 CIRCULATION PATH.
  
 1B)(3) 60.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 2) SHEET A-3 & S-1 BOTH SHOW NEW EXTERIOR DOOR OPENING.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS,
  
 2A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2B) IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  