| 2020-07-07 16:39:30 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20061271 |
| | 7/7/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-00: THE CONTRACTOR IS NOT PERMITTED BY FL. |
| | STATUTES 481 AND 489 TO MARK UP AN ARCHITECT'S PLAN. |
| | THE ARCHITECT DAVID GENGLER MAY PROVIDE AN |
| | ELECTRONICALLY SIGNED AND SEALED GAS PIPING LAYOUT |
| | PLAN, OR THE CONTRACTOR MAY PROVIDE A SEPARATE LAYOUT |
| | PLAN WITH HIS SIGNATURE ON THE PLAN- SECTION 107.2.1 |
| | WPB. |
| | |
| | 2) BASED ON THE APPROVED PLANS UNDER PERMIT-20020841, A |
| | SEPARATE PERMIT WAS REQUIRED FOR GAS. THE APPROVED |
| | PLANS INDICATED A GAS BBQ WAS BEING INSTALLED IN THE |
| | OUTDOOR KITCHEN. IT IS MANDATORY THAT THE BBQ AND ANY |
| | OTHER GAS-FIRED APPLIANCES EITHER NEW OR EXISTING ARE |
| | INCLUDED IN THE GAS PLANS AND ISOMETRIC DRAWING TO |
| | ENSURE A SAFE OPERATING SYSTEM WILL BE INSTALLED- |
| | SECTION G2412.4 FBC RES. |
| | |
| | COMMENTS 3-5 BELOW ARE SPECIFIC TO THE CURRENT |
| | SUBMITTAL WHICH MUST BE MODIFIED PER COMMENT #2. |
| | |
| | 3) GAS ISOMETRIC: A) PROVIDE THE TOTAL DEVELOPED LENGTH |
| | OF THE SYSTEM AND THE TOTAL BTUH LOAD- SECTIONS |
| | G2413.4.1 AND G2413.3 FBC RES. B) PROVIDE THE SIZE AND |
| | TYPE OF GAS PIPE AT THE METER THAT THE NEW CSST LINES |
| | ARE CONNECTING TO- SECTION 2413.4.1. C) SHOW THE |
| | REGULATOR AND GAS DELIVERY PRESSURE AT THE METER- |
| | SECTION G2413.2 D) ACCORDING TO TABLE 402.4(15) FBC FG |
| | OR G2413.4(5) FBC RES THE EHD 13 AND 15 CSST PIPES ARE |
| | UNDERSIZED: 160,000 BTUH = 160 CFH OF GAS. TANKLESS-1 |
| | REQUIRES AT 75 FT. AND TANKLESS-2 AT 60FT. EACH REQUIRE |
| | EHD 37. D) SIGNATURE OF THE CONTRACTOR SHALL BE ON THE |
| | REVISED ISOMETRIC DRAWING- SECTION 107.2.1 WPB. |
| | |
| | 4) UNDERGROUND CSST INSTALLATIONS SHALL BE DONE IN |
| | ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS. THE |
| | PIPE SHALL EITHER BE LISTED AND LABELED FOR DIRECT |
| | BURIAL OR BE INSTALLED IN A PROTECTIVE CONDUIT. PROVIDE |
| | INSTALLATION DETAILS AS RECOMMENDED BY THE |
| | MANUFACTURER- SEE SECTIONS G2415.2 AND G2415.11 FBC RES |
| | (404.2 & 404.11 FBC FG). |
| | |
| | 5) PROVIDE FRONT ELEVATION VIEWS OF THE TANKLESS WATER |
| | HEATERS SHOWING: A) INSTALLATION HEIGHTS ABOVE THE |
| | GRADE. B) VENT TERMINATION CLEARANCES TO OPERABLE |
| | WINDOWS AND DOORS AND AIR INLETW INTO THE BUILDING- |
| | G2427.8. C) VENT FLUE INSTALLATIONS: PROVIDE A VENTING |
| | DIAGRAM SHOWING THE TYPE AND SIZE FLUE VENT, LENGTH OF |
| | CONNECTOR (IF APPLICABLE), TOTAL LENGTH OF VENT FLUE |
| | RUN INCLUDING OFFSETS, AND TERMINATION LOCATION- |
| | SECTIONS G2427.6.1- G2427.6.11 FBC RES. PLEASE INDICATE |
| | VENT TERMINATION CLEARANCES PER SECTION G2427.6.3. |
| | |
| | 6) THE SUBMITTED TANKLESS WATER HEATER SPECS ARE |
| | INCOMPLETE AND DO NOT PROVIDE THE REQUIRED GAS INPUT |
| | PRESSURES FOR THE WATER HEATERS- SECTION G2448.1 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |