Plan Review Notes
Plan Review Notes For Permit 20061252
Permit Number 20061252
Review Stop M
Sequence Number 2
Notes
Date Text
2020-10-07 14:57:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20061252
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE LABEL DRAWINGS AS TO WHICH FLOOR IT APPLIES
 TO. FBC 107.2.1
  
 2) PLEASE IDENTIFY EACH ROOM ON THE MECHANICAL
 DRAWINGS. FBC 107.2.1
  
 3) IS THE LOCATION OF AHU-1 IN THE ATTIC? FBC EC
 R403.3.6
  
 4) PLEASE SHOW RETURN AIR DUCT SIZE FOR AHU-1 THAT IS
 RETURNING AIR FROM WHAT APPEARS TO BE A BEDROOM, AND
 THE RETURN AIR DUCT FROM AHU-3 FOR BEDROOM. FBC 107.2.1
  
 5) PLEASE SHOW THAT THE RETURN AIR PATH MEETS FBC RES
 M1602.3
  
 6) PLEASE SHOW BATHROOM EXHAUST FAN TERMINATIONS. FBC
 107.2.1
  
 7) PROVIDE SPECS FOR THE BATHROOM EXHAUST FANS. FBC RES
 M1507.4
  
 8) PLEASE SHOW DRYER DUCTS AND TERMINATION. FBC 107.2.1
  
 9) PLEASE SHOW CONDENSATE DISPOSAL. FBC RES M1411.3
  
 10) THE SUPPLY DUCT FEEDING THE OPPOSITE SIDE OF HOUSE
 FROM AHU-1 IS TIED INTO THE RETURN BOX.
  
 11) PLEASE SHOW HOW THE CONDENSING UNITS WILL BE
 SECURED. FBC RES M1307.
  
 12) PROVIDE INFORMATION ON THE RANGE. IS A HOOD GOING
 TO BE USED? IF SO PROVIDE CFM?S. FBC RES M1503.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  