| 2020-10-07 14:57:09 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20061252 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE LABEL DRAWINGS AS TO WHICH FLOOR IT APPLIES |
| | TO. FBC 107.2.1 |
| | |
| | 2) PLEASE IDENTIFY EACH ROOM ON THE MECHANICAL |
| | DRAWINGS. FBC 107.2.1 |
| | |
| | 3) IS THE LOCATION OF AHU-1 IN THE ATTIC? FBC EC |
| | R403.3.6 |
| | |
| | 4) PLEASE SHOW RETURN AIR DUCT SIZE FOR AHU-1 THAT IS |
| | RETURNING AIR FROM WHAT APPEARS TO BE A BEDROOM, AND |
| | THE RETURN AIR DUCT FROM AHU-3 FOR BEDROOM. FBC 107.2.1 |
| | |
| | 5) PLEASE SHOW THAT THE RETURN AIR PATH MEETS FBC RES |
| | M1602.3 |
| | |
| | 6) PLEASE SHOW BATHROOM EXHAUST FAN TERMINATIONS. FBC |
| | 107.2.1 |
| | |
| | 7) PROVIDE SPECS FOR THE BATHROOM EXHAUST FANS. FBC RES |
| | M1507.4 |
| | |
| | 8) PLEASE SHOW DRYER DUCTS AND TERMINATION. FBC 107.2.1 |
| | |
| | 9) PLEASE SHOW CONDENSATE DISPOSAL. FBC RES M1411.3 |
| | |
| | 10) THE SUPPLY DUCT FEEDING THE OPPOSITE SIDE OF HOUSE |
| | FROM AHU-1 IS TIED INTO THE RETURN BOX. |
| | |
| | 11) PLEASE SHOW HOW THE CONDENSING UNITS WILL BE |
| | SECURED. FBC RES M1307. |
| | |
| | 12) PROVIDE INFORMATION ON THE RANGE. IS A HOOD GOING |
| | TO BE USED? IF SO PROVIDE CFM?S. FBC RES M1503.4 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |