2020-06-29 13:02:02SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE DISTANCE FROM THE EDGE OF THE
 BUILDING TO THE EDGE OF THE SHUTTERS FOR THE SHUTTERS
 ON THE CORNERS OF THE BUILDING TO DETERMINE IF IN WIND
 ZONE 4 OR 5.
 2) SHUTTERS 3, 5, 6, 8, 9, AND 14 MAY BE IN WIND ZONE 5
 (WIND PRESSURE - 60 ON THE SHUTTER ATTACHMENT CHART
 NEEDS TO BE USED).PLEASE REVISE THE ANCHOR SCHEDULE.
 3) WHEN THE EDGE DISTANCE FOR THE TAPCON IS 2 1/2" -
 YOU NEED TO MULTIPLY THE SPACING BY .81 SEE PRODUCT
 APPROVAL PAGE 13 OF 20 (ANCHOR EDGE DISTANCE IS 3 1/2"
 TO USE THE SPACING SHOWN ON THE CHART) PLEASE REVIEW
 THE SPACING SHOWN ON THE ATTACHMENT SCHEDULE PROVIDED.
  