| 2020-06-29 13:02:02 | SHUTTERS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE DISTANCE FROM THE EDGE OF THE | | | BUILDING TO THE EDGE OF THE SHUTTERS FOR THE SHUTTERS | | | ON THE CORNERS OF THE BUILDING TO DETERMINE IF IN WIND | | | ZONE 4 OR 5. | | | 2) SHUTTERS 3, 5, 6, 8, 9, AND 14 MAY BE IN WIND ZONE 5 | | | (WIND PRESSURE - 60 ON THE SHUTTER ATTACHMENT CHART | | | NEEDS TO BE USED).PLEASE REVISE THE ANCHOR SCHEDULE. | | | 3) WHEN THE EDGE DISTANCE FOR THE TAPCON IS 2 1/2" - | | | YOU NEED TO MULTIPLY THE SPACING BY .81 SEE PRODUCT | | | APPROVAL PAGE 13 OF 20 (ANCHOR EDGE DISTANCE IS 3 1/2" | | | TO USE THE SPACING SHOWN ON THE CHART) PLEASE REVIEW | | | THE SPACING SHOWN ON THE ATTACHMENT SCHEDULE PROVIDED. | | | |
|