Plan Review Notes
Plan Review Notes For Permit 20061205
Permit Number 20061205
Review Stop B
Sequence Number 2
Notes
Date Text
2020-08-19 09:15:22PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2 ND BUILDING REVIEW DENIED:
  
 THE GENERATOR PAD SPECIFICATION, SUBMITTED ON PAPER, BY
 AMERICAST DOES NOT:
 1) FAILED, INDICATE COMPATIBILITY WITH PERKINS
 GENERATOR AGP56
 2) OK, WIND SPEED AND EXPOSURE SHOWN ON THE SUBMITTAL
 ARE ABOVE THE REQUIRED WIND SPEED.
 3) FAILED, HAVE AN ORIGINAL SIGNATURE AND SEAL BY
 ENGINEER
  
 PLEASE SUBMIT THE GENERATOR PAD SPECIFICATIONS WITH THE
 REQUIREMENTS NOTED ABOVE.