| Plan Review Notes For Permit 20061205 |
| Permit Number |
20061205 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-08-19 09:15:22 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561?805?6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 2 ND BUILDING REVIEW DENIED: | | | | | | THE GENERATOR PAD SPECIFICATION, SUBMITTED ON PAPER, BY | | | AMERICAST DOES NOT: | | | 1) FAILED, INDICATE COMPATIBILITY WITH PERKINS | | | GENERATOR AGP56 | | | 2) OK, WIND SPEED AND EXPOSURE SHOWN ON THE SUBMITTAL | | | ARE ABOVE THE REQUIRED WIND SPEED. | | | 3) FAILED, HAVE AN ORIGINAL SIGNATURE AND SEAL BY | | | ENGINEER | | | | | | PLEASE SUBMIT THE GENERATOR PAD SPECIFICATIONS WITH THE | | | REQUIREMENTS NOTED ABOVE. |
|