| Plan Review Notes For Permit 20061188 |
| Permit Number |
20061188 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-07-15 11:39:53 | SHUTTERS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) THE SHUTTER ATTACHMENT SCHEDULE IS NOT FILLED IN | | | CORRECTLY - | | | 2) ON THE SCHEDULE WHERE IT SAYS "SHUTTER MOUNTING | | | CONNECTION TYPE PER PRODUCT APPROVAL = SHOW THE MOUNT | | | TYPE USED (A, B, C, D ETC) FOR THE TOP/BOTTOM (C/F OR | | | C/C ETC.) | | | 3) ON THE SCHEDULE WHERE IT SAYS "MINIMUM EDGE | | | DISTANCE" THIS IS FOR THE ANCHOR (CENTER OF ANCHOR TO | | | EDGE OF OPENING) LIKE (3 1/2"). WHAT EVER EDGE DISTANCE | | | YOU ARE USING AS APPROVED BY THE PRODUCT APPROVAL. | | | |
|