| 2020-07-28 18:05:30 | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | 7/28/2020 2ND GAS REVIEW **DENIED** WITH COMMENTS NOTE |
| | - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1-SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | PIPE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC |
| | FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS |
| | RES SECS. G2413.4.1, G2413.4.2. |
| | |
| | 2- SUBMIT A DETAIL SHOWING THE TYPE OF MATERIAL, SIZE, |
| | TERMINATION POINTS OF THE GAS SLEEVES PER 2017 FBC FUEL |
| | GAS SEC 404.4 |
| | |
| | 3- WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |