| Date |
Text |
| 2020-07-15 13:08:50 | PLAN REVIEW ? GENERATOR - ? FUEL GAS |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | SOW IS THE INSTALLATION OF A 48KW GENERATOR |
| | |
| | REVIEW OF CITY RECORDS INDICATES THERE IS AN EXISTING |
| | NG SERVICE AT THE RESIDENCE |
| | |
| | |
| | |
| | |
| | 1) GAS ISOMETRIC DRAWING: |
| | |
| | 1A) THE DRAWING IS INCOMPLETE AND MUST BE MODIFIED TO |
| | SHOW THE ENTIRE SYSTEM INCLUDING ALL BRANCH PIPES FROM |
| | THE METER TO THE MOST REMOTE OUTLET. THE BTUH LOAD OF |
| | EACH APPLIANCE AND THE LOCATIONS OF REGULATORS SHALL BE |
| | INDICATED ON THE DRAWING- SECTIONS G2412.3 & G2412.4 |
| | FBC RES. |
| | |
| | EXCEPTION PER TIM LARGE CHIEF PLUMBING INSPECTOR - IF |
| | IT IS NOT POSSIBLE TO GAIN ACCESS TO THE DWELLING UNIT |
| | YOU MAY ESTIMATE THE TOTAL BTUH OF THE EXISTING |
| | APPLIANCES. |
| | |
| | NOTE: THIS PLUMBING CONTRATOR INSTALLED THE GAS |
| | APPLIANCES FOR THE NEW RESIDENCE. I CAN PROVIDE A COPY |
| | OF THE EXISTING GAS RISER IF NEEDED. |
| | |
| | 1B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM |
| | FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH |
| | LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & |
| | G2413.4.3. PROVIDED |
| | |
| | 1B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE |
| | OUTLET OF THE REGULATOR- SECTION G2421.1 |
| | |
| | 1C) PROVIDE THE BTUH LOAD OF THE GENERATOR. G2413.2 FBC |
| | RES. |
| | |
| | 1D) PROVIDE GENERATOR SPECS. G2413.2 FBC RES. |
| | |
| | 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH |
| | MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET |
| | AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION |
| | G2421.1. |
| | |