Plan Review Notes
Plan Review Notes For Permit 20061133
Permit Number 20061133
Review Stop B
Sequence Number 2
Notes
Date Text
2020-07-07 09:24:48WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061133
 ADD: 701 S. OLIVE AVE. # 813
 CONT: CONSTRUCTION SOLUTIONS
 TEL: 561-337-7773
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JULY 07TH/ 2020
 ACTION: DENIED
  
 1) 2ND REQUEST FOR A FLOOR PLAN. THE SUBMITTED FLOOR
 PLAN IN THE BOTTOM RIGHT HAND CORNER INDICATED THIS IS
 A COPIED PLAN, PLAN DATE FROM 2004 BY ARCHIECT B C
 ARCHITECTURE.
 THE PLANS DRAWN BY DESIGN PROFESSIONAL, ARCHITECTS &
 ENGINEERS BOTH HAVE TO HAVE TITLEBLOCKS WHEN BEING
 SUBMITTED TO THE BUILDING DEPARTMENT. FL.
 ADMINISTRATIVE CODE 61G1-16.004.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ARCHITECTS PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
  
 1ST PLAN REVIEW. THE PERMIT APPLICATION INDICATES UNDER
 THE SCOPE OF WORK THE INSTALLATION OF 420 SQ. FT. OF
 FLOOR INSULATION, PROFLEX 90. PLEASE NOTE THERE IS NO
 FLOOR PLAN INDICATING THE LOCATION WITHIN THE TENANT
 SUITE WHERE THE WORK IS TO OCCUR.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2) 2ND REQUEST. PLANS TO BE SUBMITTED NEED TO COMPLY
 WITH 107.2.1.3. QUALITY OF PLANS. BUILDING PLANS SHALL
 BE DRAWN TO A 1/8TH INCH SCALE ON SUBSTANTIAL PAPER OR
 OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR
 THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 3)2ND REQUEST. IF PLANS ARE DRAWN BY THE CONTRACTOR.
 PLANS DRAWN BY CONTRACTORS. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH
 TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER
 THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR
 NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE
 DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED
 AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO
 SUBMIT ALL THESE TRADES UNDER ONE SHEET.
  
 4)2ND REQUEST. NOTE THIS BUILDING HAS 7 INCH THICK
 SLABS, 6 INCH REPORTS ARE REQUIRED. THE FLOOR PLAN TO
 BE SUBMITTED MUST INDICATE THE TYPE OF FLOOR FINISH
 THAT IS TO BE ADHERED TO THE FLOOR. SPECIFY THE ACTUAL
 PRODUCT BY FULL NAME. WITHIN THE TEST REPORTS TO BE
 SUBMITTED NO INSULATION IN A DROPPED CEILING, NO
 DROPPED CEILINGS.
 FLOOR INSULATION (FBC-B 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
 TYPE I AND II BUILDINGS
  
 4A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved