| | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20061133 |
| | ADD: 701 S. OLIVE AVE. # 813 |
| | CONT: CONSTRUCTION SOLUTIONS |
| | TEL: 561-337-7773 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. JULY 05TH/ 2020 |
| | ACTION: DENIED |
| | 1) THE PERMIT APPLICATION INDICATES UNDER THE SCOPE OF |
| | WORK THE INSTALLATION OF 420 SQ. FT. OF FLOOR |
| | INSULATION, PROFLEX 90. PLEASE NOTE THERE IS NO FLOOR |
| | PLAN INDICATING THE LOCATION WITHIN THE TENANT SUITE |
| | WHERE THE WORK IS TO OCCUR. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1. |
| | CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| | INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2) PLANS TO BE SUBMITTED NEED TO COMPLY WITH 107.2.1.3. |
| | QUALITY OF PLANS. BUILDING PLANS SHALL BE DRAWN TO A |
| | 1/8TH INCH SCALE ON SUBSTANTIAL PAPER OR OTHER |
| | ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH |
| | THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR THE PLANS |
| | AND SPECIFICATIONS IN ORDER TO PROVIDE CONFORMITY TO |
| | ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE |
| | SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, |
| | OR OTHER ITEMS RELATED TO RECORD MANAGEMENT. ELECTRONIC |
| | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| | OF FLORIDA STATUTES. |
| | |
| | 3) PLANS DRAWN BY CONTRACTORS. 107.3.4.3 CERTIFICATION |
| | BY CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED |
| | PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/ |
| | MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE |
| | CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT |
| | TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE |
| | SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) |
| | THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| | THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH |
| | TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER |
| | THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR |
| | NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE |
| | DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED |
| | AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO |
| | SUBMIT ALL THESE TRADES UNDER ONE SHEET. |
| | |
| | 4) THE FLOOR PLAN TO BE SUBMITTED MUST INDICATE THE |
| | TYPE OF FLOOR FINISH THAT IS TO BE ADHERED TO THE |
| | FLOOR. SPECIFY THE ACTUAL PRODUCT BY FULL NAME. WITHIN |
| | THE TEST REPORTS TO BE SUBMITTED NO INSULATION IN A |
| | DROPPED CEILING, NO DROPPED CEILINGS. |
| | FLOOR INSULATION (FBC-B 2017) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING |
| | COMPLIANCE WITH: |
| | TYPE I AND II BUILDINGS |
| | |
| | 4A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 4B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 4C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |