| 2020-09-17 11:54:41 | 4TH REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20061121` |
| | 9/17/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 3.0MP: THE WASTE FROM THE SINK PUMP CANNOT |
| | DRAIN INTO THE INDIVIDUAL FIXTURE VENT FOR THE MOP |
| | SINK- SECTIONS 712.3.5 AND 905.1 FBC P. IF THE |
| | INTENTION IS TO SHOW A CONNECTION INTO A WASTE STACK, |
| | THEN THE WASTE STACK SHALL RUN VERTICALLY FROM THE |
| | HORIZONTAL DRAIN, AND THE MOP SINK AND KITCHEN SINK |
| | FIXTURE DRAINS WOULD EACH CONNECT INDIVIDUALLY INTO THE |
| | WASTE STACK. THIS MAY NOT BE POSSIBLE IF THE |
| | CONFIGURATION OF THE MOP SINK VENT IS ACCURATELY SHOWN |
| | AND YOU ARE ATTEMPTING TO TURN THE VENT INTO A WASTE |
| | STACK; OR IF THE FIXTURE DRAIN CONNECTS HORIZONTALLY TO |
| | THE DRAIN BELOW THE SLAB, THE VENT MUST BE MAINTAINED |
| | OPEN TO THE AIR WITHOUT ANY OTHER WASTE DISCHARGE INTO |
| | IT. ULTIMATELY A SEPARATE WASTE STACK MAY HAVE TO BE |
| | INSTALLED TO ACCOMMODATE THE KITCHEN SINK. PLEASE NOTE |
| | THE STACK VENT ABOVE SHALL BE THE SAME DIAMETER AS THE |
| | WASTE STACK- SEE SECTIONS 913.1- 913.4 FBC P AND |
| | CORRECT THE DRAWINGS. |
| | |
| | 2) 3.0MP: PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS |
| | AND THE INSTALL GUIDELINES FOR THE LIBERTY 405 SUMP |
| | PUMP INCLUDING PUMP CURVE. PROVIDE TDH (TOTAL DYNAMIC |
| | HEAD) CALCULATION ON THE PLAN TO VERIFY ACCURATE SIZING |
| | OF THE PUMP ACCORDING TO THE CURVE- SECTION 712.3.1 FBC |
| | P. |
| | |
| | 3) 3.0MP: SHOW ON THE DRAWINGS THE LOCATIONS OF THE |
| | REQUIRED CHECK VALVE AND FULL OPEN VALVE ON THE |
| | DISCHARGE PIPING OF THE PUMP BETWEEN THE PUMP AND THE |
| | GRAVITY DRAIN. SHOW HOW ACCESS FOR WILL BE PROVIDED TO |
| | THE VALVES- SECTION 712.2 FBC P. |
| | |
| | 4) SHEET 1.0A: CONCERNING THE BREAKROOM THE |
| | ARCHITECTURAL AND MEP WORK PERFORMED IN THE ROOM CANNOT |
| | BE LABELED AS EXISTING IF NEVER LEGALLY PERMITTED. THE |
| | PLAN SHALL BE REVIEWED AND PERMITTED AS NEW IF THERE IS |
| | NO EVIDENCE OF A PERMIT OR INSPECTIONS ON RECORD FOR |
| | THE WORK PERFORMED. IT HAS ALREADY BEEN ESTABLISHED |
| | THAT THE PREVIOUS PERMIT PLANS UNDER 19051456 DID NOT |
| | SHOW THE BREAKROOM. |
| | |
| | 5) 2.0E: A REVISION TO THE APPROVED ELECTRICAL PLAN IS |
| | REQUIRED TO PROVIDE A RECEPTACLE UNDER THE SINK FOR THE |
| | SUMP PUMP- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |