2020-09-17 11:54:414TH REVIEW FBC-2017 PLUMBING
 PERMIT- 20061121`
 9/17/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3.0MP: THE WASTE FROM THE SINK PUMP CANNOT
 DRAIN INTO THE INDIVIDUAL FIXTURE VENT FOR THE MOP
 SINK- SECTIONS 712.3.5 AND 905.1 FBC P. IF THE
 INTENTION IS TO SHOW A CONNECTION INTO A WASTE STACK,
 THEN THE WASTE STACK SHALL RUN VERTICALLY FROM THE
 HORIZONTAL DRAIN, AND THE MOP SINK AND KITCHEN SINK
 FIXTURE DRAINS WOULD EACH CONNECT INDIVIDUALLY INTO THE
 WASTE STACK. THIS MAY NOT BE POSSIBLE IF THE
 CONFIGURATION OF THE MOP SINK VENT IS ACCURATELY SHOWN
 AND YOU ARE ATTEMPTING TO TURN THE VENT INTO A WASTE
 STACK; OR IF THE FIXTURE DRAIN CONNECTS HORIZONTALLY TO
 THE DRAIN BELOW THE SLAB, THE VENT MUST BE MAINTAINED
 OPEN TO THE AIR WITHOUT ANY OTHER WASTE DISCHARGE INTO
 IT. ULTIMATELY A SEPARATE WASTE STACK MAY HAVE TO BE
 INSTALLED TO ACCOMMODATE THE KITCHEN SINK. PLEASE NOTE
 THE STACK VENT ABOVE SHALL BE THE SAME DIAMETER AS THE
 WASTE STACK- SEE SECTIONS 913.1- 913.4 FBC P AND
 CORRECT THE DRAWINGS.
  
 2) 3.0MP: PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS
 AND THE INSTALL GUIDELINES FOR THE LIBERTY 405 SUMP
 PUMP INCLUDING PUMP CURVE. PROVIDE TDH (TOTAL DYNAMIC
 HEAD) CALCULATION ON THE PLAN TO VERIFY ACCURATE SIZING
 OF THE PUMP ACCORDING TO THE CURVE- SECTION 712.3.1 FBC
 P.
  
 3) 3.0MP: SHOW ON THE DRAWINGS THE LOCATIONS OF THE
 REQUIRED CHECK VALVE AND FULL OPEN VALVE ON THE
 DISCHARGE PIPING OF THE PUMP BETWEEN THE PUMP AND THE
 GRAVITY DRAIN. SHOW HOW ACCESS FOR WILL BE PROVIDED TO
 THE VALVES- SECTION 712.2 FBC P.
  
 4) SHEET 1.0A: CONCERNING THE BREAKROOM THE
 ARCHITECTURAL AND MEP WORK PERFORMED IN THE ROOM CANNOT
 BE LABELED AS EXISTING IF NEVER LEGALLY PERMITTED. THE
 PLAN SHALL BE REVIEWED AND PERMITTED AS NEW IF THERE IS
 NO EVIDENCE OF A PERMIT OR INSPECTIONS ON RECORD FOR
 THE WORK PERFORMED. IT HAS ALREADY BEEN ESTABLISHED
 THAT THE PREVIOUS PERMIT PLANS UNDER 19051456 DID NOT
 SHOW THE BREAKROOM.
  
 5) 2.0E: A REVISION TO THE APPROVED ELECTRICAL PLAN IS
 REQUIRED TO PROVIDE A RECEPTACLE UNDER THE SINK FOR THE
 SUMP PUMP- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  