| Date |
Text |
| 2020-09-09 09:47:41 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20061112 |
| | 9/9/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 1.0A: THE NOTE AT THE BREAKROOM INDICATES THE |
| | SINK WAS INSPECTED UNDER PERMIT #19051456. THE RECORD |
| | DRAWINGS THAT ARE ON FILE FOR THE PERMIT DO NOT SHOW A |
| | BREAKROOM OR SINK AT THAT LOCATION. AS PREVIOUSLY NOTED |
| | IN COMMENTS #1 & 3 PRINTED BELOW, PLUMBING PIPING AND |
| | ACCESSIBILITY DRAWINGS AND DETAILS ARE REQUIRED. |
| | 1. FAILED. SHEET C-1: NO PLUMBING PLANS HAVE BEEN |
| | SUBMITTED. INDICATE THE SUITE NUMBER BY THE ADDRESS AT |
| | THE TOP OF THE PLAN SHEET- SECTION 107.2.1 WPB. THE |
| | APPROVED PLANS UNDER PERMIT- 19051456 DO NOT SHOW A |
| | BREAKROOM COUNTER AND SINK, A REFRIGERATOR, AND THE |
| | DRINKING FOUNTAIN. AS PREVIOUSLY REQUESTED, PROVIDE |
| | PLUMBING PLANS FOR THE NEW INSTALLATIONS. |
| | 3. FAILED. SHEET 1.0A AND PLUMBING PLAN: LABEL THE |
| | SUITE NUMBERS ON THE PLANS, AND LABEL THE RESTROOMS FOR |
| | THE GYM OCCUPANCY AS EITHER MALE OR FEMALE- SECTIONS |
| | 403.2 & 403.2.1 FBC P. PROVIDE A PLUMBING FIXTURE AND |
| | DEVICE SCHEDULE ON THE PLAN- SECTION 107.2.1 WPB & |
| | SECTION 405.9 FBC P. THE REQUESTED PLUMBING FIXTURE |
| | SCHEDULE WAS NOT PROVIDED. NEW DETAILS HAVE BEEN |
| | PROVIDED FOR ACCESSIBLE FIXTURES THAT SHALL BE IN |
| | COMPLIANCE WITH THE FBC-17 ACCESSIBILITY CODE. PLEASE |
| | PROVIDE THE CODE DATA AND PROVIDE AN ELEVATION AND SIDE |
| | VIEW DRAWING OF THE NEW COUNTERTOP AND SINK- SECTIONS |
| | 606.3 AND 309. |
| | |
| | 2) SHEET 1.0A: COMMENT #3K FROM THE PREVIOUS REVIEW |
| | PRINTED BELOW STILL EXISTS. THE SMALLER OF THE TWO |
| | RESTROOMS IN QUESTION IS NOW IDENTIFIED ON THE PLAN AS |
| | EX. WOMEN. AS NOTED BELOW THE DOOR SHALL NOT SWING INTO |
| | THE CLEAR FLOOR SPACE OF THE LAVATORY UNLESS MEETING |
| | EXCEPTION 2 UNDER SECTION 603.2.3 FBC ACC. |
| | K. FAILED. PLEASE NOTE: THE PLAN APPEARS TO SHOW THE |
| | DOOR INTO THE SMALLER OF THE TWO RESTROOMS WILL SWING |
| | INTO THE CLEAR FLOOR SPACE OF THE LAVATORY- SECTION |
| | 603.2.3 FBC ACC. THE NEW ACCESSIBILITY DETAILS SHOW THE |
| | DOOR SWINGING OUT WHICH DOES NOT MATCH THE FLOOR PLAN. |
| | PLEASE SEE EXCEPTIONS UNDER SECTION 603.2.3. |
| | |
| | 3) SHEET 1.0A: COMMENT #7 FROM THE PREVIOUS REVIEW |
| | STILL EXISTS. FIGURE G ON THE PLAN IS MISLABELED AS A |
| | LATCH SIDE INSTEAD OF A HINGE SIDE APPROACH, BUT THE |
| | MANEUVERING CLEARANCE FOR THE APPROACH SHOWN DOES NOT |
| | MATCH THE FLOOR PLAN LAYOUT BECAUSE THE 22? CLEARANCE |
| | AT THE HINGE SIDE HAS NOT BEEN PROVIDED. THERE APPEARS |
| | TO BE APPROXIMATELY 3 OR 4 INCH CLEARANCE. FOR A |
| | WHEELCHAIR TO USE THE FIGURE G APPROACH AS DEPICTED |
| | WOULD REQUIRE THE WHEELCHAIR TO ENTER THE CORRIDOR AND |
| | THEN TURN AROUND AND THERE IS INADEQUATE TURNING SPACE |
| | AS REQUIRED BY SECTION 304.3 |
| | 7. FAILED. 1.0A: SHOW THE MANEUVERING CLEARANCES AT THE |
| | RESTROOM DOORS- REFER TO FIGURES 404.2.1 FBC ACC. |
| | PROVIDE DIMENSIONS ON THE PLAN TO VERIFY COMPLIANCE. |
| | CLEARANCE DIAGRAMS AND DIMENSIONS NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |