2020-09-09 09:47:413RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20061112
 9/9/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 1.0A: THE NOTE AT THE BREAKROOM INDICATES THE
 SINK WAS INSPECTED UNDER PERMIT #19051456. THE RECORD
 DRAWINGS THAT ARE ON FILE FOR THE PERMIT DO NOT SHOW A
 BREAKROOM OR SINK AT THAT LOCATION. AS PREVIOUSLY NOTED
 IN COMMENTS #1 & 3 PRINTED BELOW, PLUMBING PIPING AND
 ACCESSIBILITY DRAWINGS AND DETAILS ARE REQUIRED.
 1. FAILED. SHEET C-1: NO PLUMBING PLANS HAVE BEEN
 SUBMITTED. INDICATE THE SUITE NUMBER BY THE ADDRESS AT
 THE TOP OF THE PLAN SHEET- SECTION 107.2.1 WPB. THE
 APPROVED PLANS UNDER PERMIT- 19051456 DO NOT SHOW A
 BREAKROOM COUNTER AND SINK, A REFRIGERATOR, AND THE
 DRINKING FOUNTAIN. AS PREVIOUSLY REQUESTED, PROVIDE
 PLUMBING PLANS FOR THE NEW INSTALLATIONS.
 3. FAILED. SHEET 1.0A AND PLUMBING PLAN: LABEL THE
 SUITE NUMBERS ON THE PLANS, AND LABEL THE RESTROOMS FOR
 THE GYM OCCUPANCY AS EITHER MALE OR FEMALE- SECTIONS
 403.2 & 403.2.1 FBC P. PROVIDE A PLUMBING FIXTURE AND
 DEVICE SCHEDULE ON THE PLAN- SECTION 107.2.1 WPB &
 SECTION 405.9 FBC P. THE REQUESTED PLUMBING FIXTURE
 SCHEDULE WAS NOT PROVIDED. NEW DETAILS HAVE BEEN
 PROVIDED FOR ACCESSIBLE FIXTURES THAT SHALL BE IN
 COMPLIANCE WITH THE FBC-17 ACCESSIBILITY CODE. PLEASE
 PROVIDE THE CODE DATA AND PROVIDE AN ELEVATION AND SIDE
 VIEW DRAWING OF THE NEW COUNTERTOP AND SINK- SECTIONS
 606.3 AND 309.
  
 2) SHEET 1.0A: COMMENT #3K FROM THE PREVIOUS REVIEW
 PRINTED BELOW STILL EXISTS. THE SMALLER OF THE TWO
 RESTROOMS IN QUESTION IS NOW IDENTIFIED ON THE PLAN AS
 EX. WOMEN. AS NOTED BELOW THE DOOR SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE OF THE LAVATORY UNLESS MEETING
 EXCEPTION 2 UNDER SECTION 603.2.3 FBC ACC.
 K. FAILED. PLEASE NOTE: THE PLAN APPEARS TO SHOW THE
 DOOR INTO THE SMALLER OF THE TWO RESTROOMS WILL SWING
 INTO THE CLEAR FLOOR SPACE OF THE LAVATORY- SECTION
 603.2.3 FBC ACC. THE NEW ACCESSIBILITY DETAILS SHOW THE
 DOOR SWINGING OUT WHICH DOES NOT MATCH THE FLOOR PLAN.
 PLEASE SEE EXCEPTIONS UNDER SECTION 603.2.3.
  
 3) SHEET 1.0A: COMMENT #7 FROM THE PREVIOUS REVIEW
 STILL EXISTS. FIGURE G ON THE PLAN IS MISLABELED AS A
 LATCH SIDE INSTEAD OF A HINGE SIDE APPROACH, BUT THE
 MANEUVERING CLEARANCE FOR THE APPROACH SHOWN DOES NOT
 MATCH THE FLOOR PLAN LAYOUT BECAUSE THE 22? CLEARANCE
 AT THE HINGE SIDE HAS NOT BEEN PROVIDED. THERE APPEARS
 TO BE APPROXIMATELY 3 OR 4 INCH CLEARANCE. FOR A
 WHEELCHAIR TO USE THE FIGURE G APPROACH AS DEPICTED
 WOULD REQUIRE THE WHEELCHAIR TO ENTER THE CORRIDOR AND
 THEN TURN AROUND AND THERE IS INADEQUATE TURNING SPACE
 AS REQUIRED BY SECTION 304.3
 7. FAILED. 1.0A: SHOW THE MANEUVERING CLEARANCES AT THE
 RESTROOM DOORS- REFER TO FIGURES 404.2.1 FBC ACC.
 PROVIDE DIMENSIONS ON THE PLAN TO VERIFY COMPLIANCE.
 CLEARANCE DIAGRAMS AND DIMENSIONS NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  