| 2020-09-09 13:19:04 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20061121 |
| | ADD: 2711 EXCHANGE CT. SUITE: B |
| | CONT: EDMON WALSH CONSTRUCTION |
| | TEL: ??? |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | 3RD REVIEW |
| | DATE: WED. SEPT. 09TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. 2017 FBC-ACCESSIBILITY CODE SECTION |
| | CLEARANCES AT WATER CLOSETS. 604.3 CLEARANCE. |
| | |
| | 1A-1F) COMPLIED. |
| | |
| | 1G) PLEASE ALSO REVIEW THE PLUMBING PLANS EXAMINERS |
| | COMMENTS IN REGARDS TO THE BREAK ROOM SINK AND PERMIT |
| | 19051456. |
| | 2ND ROUND COMMENT. THE BREAK ROOM ALSO SHOWS AS |
| | EXISTING, PLEASE SHOW HOW COMPLIANCE WITH SECTION 606 |
| | SINKS. 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 |
| | HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED WITH |
| | THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE |
| | 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 1H) RESPONSE DOES NOT ADDRESS RECEPTION DESK. THE PLANS |
| | SHOW A RECEPTION DESK PLEASE PROVIDE HOW COMPLIANCE |
| | WITH SECTIONS: |
| | |
| | CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK |
| | WRITING SURFACES. WHERE PROVIDED, CHECK WRITING |
| | SURFACES SHALL COMPLY WITH 902.3. 902.3HEIGHT. THE TOPS |
| | OF WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM |
| | AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR |
| | OR GROUND. |
| | SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION. |
| | UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE |
| | SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL |
| | APPROACH TO AN ELEMENT. |
| | |
| | 2) 2ND REQUEST, RESPONSE LETTER STATE NOTES ADDED TO |
| | FLOOR PLAN, FRP TO THE MOP SINK AREA AND TILE TO THE |
| | RESTROOM WALLS. RESPONSE DOES NOT INDICATE WHICH PLAN |
| | SHEET NOTES WERE ADDED BUT COULD NOT FIND THE NEW NOTES |
| | ON THE COVERSHEET, A1.0 OR A1.1. |
| | NEW COMMENT. PLEASE NOTE THIS IS A CHANGE OF |
| | INTERPRETATION FROM THE BUILDING OFFICIAL ROBERT BROWN. |
| | EPOXY PAINTED SURFACES NO LONGER IS APPROVED AS A |
| | NON-ABSORBENT SURFACE FOR SERVICE SINKS, URINALS AND |
| | WATER CLOSETS. |
| | 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. WALLS & |
| | PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS, AND |
| | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT |
| | SURFACE TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE |
| | FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL |
| | USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT |
| | ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |