| Date |
Text |
| 2020-08-17 13:11:49 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20061112 |
| | 8/17/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE |
| | MARKED AS PASSED OR FAILED. ADDITIONAL NOTES IN CAPITOL |
| | LETTERS ARE ADDED TO FAILED COMMENTS |
| | |
| | 1) FAILED. SHEET C-1: NO PLUMBING PLANS HAVE BEEN |
| | SUBMITTED. INDICATE THE SUITE NUMBER BY THE ADDRESS AT |
| | THE TOP OF THE PLAN SHEET- SECTION 107.2.1 WPB. THE |
| | APPROVED PLANS UNDER PERMIT- 19051456 DO NOT SHOW A |
| | BREAKROOM COUNTER AND SINK, A REFRIGERATOR, AND THE |
| | DRINKING FOUNTAIN. AS PREVIOUSLY REQUESTED PROVIDE |
| | PLUMBING PLANS FOR THE NEW INSTALLATIONS. |
| | |
| | 2) FAILED. C-1: CORRECT THE PLUMBING FIXTURE SCHEDULE |
| | INDICATING A WATER COOLER TO INDICATE A DRINKING |
| | FOUNTAIN, AND REFER TO SECTION 211.1.2 FBC ACC, AND |
| | TABLE 404.3 FBC P- NO FEWER THAN TWO DRINKING FOUNTAINS |
| | SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY |
| | WITH SECTIONS 602.1 & 602.6 FBC ACC, AND ONE SHALL |
| | COMPLY WITH 602.7. SECTION 602.7 REQUIRES THAT SPOUT |
| | OUTLETS FOR STANDING PERSONS SHALL BE 38 INCHES MINIMUM |
| | AND 43 INCHES MAXIMUM FROM THE FINISHED FLOOR. REVISE |
| | THE PLANS TO SHOW COMPLIANCE AND PROVIDE THESE DETAILS: |
| | THE DETAILS BELOW ARE PASSED HOWEVER ONLY ONE DRINKING |
| | FOUNTAIN IS SHOWN ON THE FLOOR PLANS, AND NO PLUMBING |
| | PLANS HAVE BEEN PROVIDED. |
| | A) PASSED. THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS |
| | FOR FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC |
| | ACC. |
| | B) PASSED. KNEE AND TOE CLEARANCES- SECTION 306. |
| | C) PASSED. SPOUT HEIGHT AND SPOUT LOCATION- SECTION |
| | 602.4 AND 602.5. |
| | |
| | 3) FAILED. SHEET 1.0A AND PLUMBING PLAN: LABEL THE |
| | SUITE NUMBERS ON THE PLANS, AND LABEL THE RESTROOMS FOR |
| | THE GYM OCCUPANCY AS EITHER MALE OR FEMALE- SECTIONS |
| | 403.2 & 403.2.1 FBC P. PROVIDE A PLUMBING FIXTURE AND |
| | DEVICE SCHEDULE ON THE PLAN- SECTION 107.2.1 WPB & |
| | SECTION 405.9 FBC P. THE REQUESTED PLUMBING FIXTURE |
| | SCHEDULE WAS NOT PROVIDED. NEW DETAILS HAVE BEEN |
| | PROVIDED FOR ACCESSIBLE FIXTURES THAT SHALL BE IN |
| | COMPLIANCE WITH THE FBC-17 ACCESSIBILITY CODE. PLEASE |
| | PROVIDE THE CODE DATA AND PROVIDE AN ELEVATION AND SIDE |
| | VIEW DRAWING OF THE NEW COUNTERTOP AND SINK- SECTIONS |
| | 606.3 AND 309. |
| | |
| | 4) PASSED 4A- 4J. 1.0A: PROVIDE ENLARGED DIMENSIONED |
| | DRAWINGS OF THE ACCESSIBLE RESTROOMS INDICATING: |
| | A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS- |
| | SECTION 604.3 FBC ACC. |
| | B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES- |
| | SECTION 606.2 |
| | C) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS |
| | OR PARTITIONS- SECTION 604.2. |
| | D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | E) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE |
| | FINISHED FLOOR- SECTION 606.3 |
| | F) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 306. |
| | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECTION 604.5 |
| | H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- |
| | SECTION 604.6. |
| | I) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR |
| | PAPER DISPENSERS- SECTION 604.7 |
| | J) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3 |
| | K) FAILED. PLEASE NOTE: THE PLAN APPEARS TO SHOW THE |
| | DOOR INTO THE SMALLER OF THE TWO RESTROOMS WILL SWING |
| | INTO THE CLEAR FLOOR SPACE OF THE LAVATORY- SECTION |
| | 603.2.3 FBC ACC. THE NEW ACCESSIBILITY DETAILS SHOW THE |
| | DOOR SWINGING OUT WHICH DOES NOT MATCH THE FLOOR PLAN. |
| | PLEASE SEE EXCEPTIONS UNDER SECTION 603.2.3. |
| | |
| | 5) FAILED. 1.0A: SEE COMMENT 2 ABOVE AND SHOW THE |
| | LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS. IDENTIFY |
| | ALL PLUMBING FIXTURES, APPLIANCES, AND EQUIPMENT SHOWN |
| | ON THE PLANS AS EITHER NEW OR EXISTING- SECTION 107.2.1 |
| | WPB. ONLY ONE DRINKING FOUNTAIN IS PROVIDED- TWO ARE |
| | REQUIRED- SEE COMMENT 2. |
| | |
| | 6) PASSED. 1.0A AND PLUMBING PLAN: INDICATE HOW HOT |
| | WATER IS BEING PROVIDED TO THE MOP SINK, AND HOW |
| | TEMPERED WATER IS BEING PROVIDED TO THE LAVATORIES PER |
| | SECTIONS 416.5 & 607.1 FBC P. PLEASE NOTE THAT TEMPERED |
| | SHALL BE SUPPLIED THROUGH A WATER TEMPERATURE LIMITING |
| | DEVICE THAT CONFORMS TO ASSE 1070- SECTION 607.1.2 FBC |
| | P. |
| | |
| | 7) FAILED. 1.0A: SHOW THE MANEUVERING CLEARANCES AT THE |
| | RESTROOM DOORS- REFER TO FIGURES 404.2.1 FBC ACC. |
| | PROVIDE DIMENSIONS ON THE PLAN TO VERIFY COMPLIANCE. |
| | CLEARANCE DIAGRAMS AND DIMENSIONS NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |