Plan Review Notes
Plan Review Notes For Permit 20061121
Permit Number 20061121
Review Stop P
Sequence Number 2
Notes
Date Text
2020-08-17 13:11:492ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20061112
 8/17/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE
 MARKED AS PASSED OR FAILED. ADDITIONAL NOTES IN CAPITOL
 LETTERS ARE ADDED TO FAILED COMMENTS
  
 1) FAILED. SHEET C-1: NO PLUMBING PLANS HAVE BEEN
 SUBMITTED. INDICATE THE SUITE NUMBER BY THE ADDRESS AT
 THE TOP OF THE PLAN SHEET- SECTION 107.2.1 WPB. THE
 APPROVED PLANS UNDER PERMIT- 19051456 DO NOT SHOW A
 BREAKROOM COUNTER AND SINK, A REFRIGERATOR, AND THE
 DRINKING FOUNTAIN. AS PREVIOUSLY REQUESTED PROVIDE
 PLUMBING PLANS FOR THE NEW INSTALLATIONS.
  
 2) FAILED. C-1: CORRECT THE PLUMBING FIXTURE SCHEDULE
 INDICATING A WATER COOLER TO INDICATE A DRINKING
 FOUNTAIN, AND REFER TO SECTION 211.1.2 FBC ACC, AND
 TABLE 404.3 FBC P- NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH SECTIONS 602.1 & 602.6 FBC ACC, AND ONE SHALL
 COMPLY WITH 602.7. SECTION 602.7 REQUIRES THAT SPOUT
 OUTLETS FOR STANDING PERSONS SHALL BE 38 INCHES MINIMUM
 AND 43 INCHES MAXIMUM FROM THE FINISHED FLOOR. REVISE
 THE PLANS TO SHOW COMPLIANCE AND PROVIDE THESE DETAILS:
 THE DETAILS BELOW ARE PASSED HOWEVER ONLY ONE DRINKING
 FOUNTAIN IS SHOWN ON THE FLOOR PLANS, AND NO PLUMBING
 PLANS HAVE BEEN PROVIDED.
 A) PASSED. THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS
 FOR FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC
 ACC.
 B) PASSED. KNEE AND TOE CLEARANCES- SECTION 306.
 C) PASSED. SPOUT HEIGHT AND SPOUT LOCATION- SECTION
 602.4 AND 602.5.
  
 3) FAILED. SHEET 1.0A AND PLUMBING PLAN: LABEL THE
 SUITE NUMBERS ON THE PLANS, AND LABEL THE RESTROOMS FOR
 THE GYM OCCUPANCY AS EITHER MALE OR FEMALE- SECTIONS
 403.2 & 403.2.1 FBC P. PROVIDE A PLUMBING FIXTURE AND
 DEVICE SCHEDULE ON THE PLAN- SECTION 107.2.1 WPB &
 SECTION 405.9 FBC P. THE REQUESTED PLUMBING FIXTURE
 SCHEDULE WAS NOT PROVIDED. NEW DETAILS HAVE BEEN
 PROVIDED FOR ACCESSIBLE FIXTURES THAT SHALL BE IN
 COMPLIANCE WITH THE FBC-17 ACCESSIBILITY CODE. PLEASE
 PROVIDE THE CODE DATA AND PROVIDE AN ELEVATION AND SIDE
 VIEW DRAWING OF THE NEW COUNTERTOP AND SINK- SECTIONS
 606.3 AND 309.
  
 4) PASSED 4A- 4J. 1.0A: PROVIDE ENLARGED DIMENSIONED
 DRAWINGS OF THE ACCESSIBLE RESTROOMS INDICATING:
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SECTION 604.3 FBC ACC.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SECTION 606.2
 C) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 OR PARTITIONS- SECTION 604.2.
 D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 E) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 F) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 306.
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS-
 SECTION 604.6.
 I) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 PAPER DISPENSERS- SECTION 604.7
 J) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3
 K) FAILED. PLEASE NOTE: THE PLAN APPEARS TO SHOW THE
 DOOR INTO THE SMALLER OF THE TWO RESTROOMS WILL SWING
 INTO THE CLEAR FLOOR SPACE OF THE LAVATORY- SECTION
 603.2.3 FBC ACC. THE NEW ACCESSIBILITY DETAILS SHOW THE
 DOOR SWINGING OUT WHICH DOES NOT MATCH THE FLOOR PLAN.
 PLEASE SEE EXCEPTIONS UNDER SECTION 603.2.3.
  
 5) FAILED. 1.0A: SEE COMMENT 2 ABOVE AND SHOW THE
 LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS. IDENTIFY
 ALL PLUMBING FIXTURES, APPLIANCES, AND EQUIPMENT SHOWN
 ON THE PLANS AS EITHER NEW OR EXISTING- SECTION 107.2.1
 WPB. ONLY ONE DRINKING FOUNTAIN IS PROVIDED- TWO ARE
 REQUIRED- SEE COMMENT 2.
  
 6) PASSED. 1.0A AND PLUMBING PLAN: INDICATE HOW HOT
 WATER IS BEING PROVIDED TO THE MOP SINK, AND HOW
 TEMPERED WATER IS BEING PROVIDED TO THE LAVATORIES PER
 SECTIONS 416.5 & 607.1 FBC P. PLEASE NOTE THAT TEMPERED
 SHALL BE SUPPLIED THROUGH A WATER TEMPERATURE LIMITING
 DEVICE THAT CONFORMS TO ASSE 1070- SECTION 607.1.2 FBC
 P.
  
 7) FAILED. 1.0A: SHOW THE MANEUVERING CLEARANCES AT THE
 RESTROOM DOORS- REFER TO FIGURES 404.2.1 FBC ACC.
 PROVIDE DIMENSIONS ON THE PLAN TO VERIFY COMPLIANCE.
 CLEARANCE DIAGRAMS AND DIMENSIONS NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  