| Date |
Text |
| 2020-07-17 10:14:57 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20061112 |
| | 7/17/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET C-1: NO PLUMBING PLANS HAVE BEEN SUBMITTED. |
| | INDICATE THE SUITE NUMBER BY THE ADDRESS AT THE TOP OF |
| | THE PLAN SHEET- SECTION 107.2.1 WPB. |
| | |
| | 2) C-1: CORRECT THE PLUMBING FIXTURE SCHEDULE |
| | INDICATING A WATER COOLER TO INDICATE A DRINKING |
| | FOUNTAIN, AND REFER TO SECTION 211.1.2 FBC ACC, AND |
| | TABLE 404.3 FBC P- NO FEWER THAN TWO DRINKING FOUNTAINS |
| | SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY |
| | WITH SECTIONS 602.1 ? 602.6 FBC ACC, AND ONE SHALL |
| | COMPLY WITH 602.7. SECTION 602.7 REQUIRES THAT SPOUT |
| | OUTLETS FOR STANDING PERSONS SHALL BE 38 INCHES MINIMUM |
| | AND 43 INCHES MAXIMUM FROM THE FINISHED FLOOR. REVISE |
| | THE PLANS TO SHOW COMPLIANCE AND PROVIDE THESE DETAILS: |
| | A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC. |
| | B) KNEE AND TOE CLEARANCES- SECTION 306. |
| | C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND |
| | 602.5. |
| | |
| | 3) SHEET 1.0A AND PLUMBING PLAN: LABEL THE SUITE |
| | NUMBERS ON THE PLANS, AND LABEL THE RESTROOMS FOR THE |
| | GYM OCCUPANCY AS EITHER MALE OR FEMALE- SECTIONS 403.2 |
| | & 403.2.1 FBC P. PROVIDE A PLUMBING FIXTURE AND DEVICE |
| | SCHEDULE ON THE PLAN- SECTION 107.2.1 WPB & SECTION |
| | 405.9 FBC P. |
| | |
| | 4) 1.0A: PROVIDE ENLARGED DIMENSIONED DRAWINGS OF THE |
| | ACCESSIBLE RESTROOMS INDICATING: |
| | A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS- |
| | SECTION 604.3 FBC ACC. |
| | B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES- |
| | SECTION 606.2 |
| | C) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS |
| | OR PARTITIONS- SECTION 604.2. |
| | D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | E) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE |
| | FINISHED FLOOR- SECTION 606.3 |
| | F) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 306. |
| | G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECTION 604.5 |
| | H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- |
| | SECTION 604.6. |
| | I) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR |
| | PAPER DISPENSERS- SECTION 604.7 |
| | J) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3 |
| | K) PLEASE NOTE: THE PLAN APPEARS TO SHOW THE DOOR INTO |
| | THE SMALLER OF THE TWO RESTROOMS WILL SWING INTO THE |
| | CLEAR FLOOR SPACE OF THE LAVATORY- SECTION 603.2.3 FBC |
| | ACC. |
| | |
| | 5) 1.0A: SEE COMMENT 2 ABOVE AND SHOW THE LOCATIONS OF |
| | THE REQUIRED DRINKING FOUNTAINS. IDENTIFY ALL PLUMBING |
| | FIXTURES, APPLIANCES, AND EQUIPMENT SHOWN ON THE PLANS |
| | AS EITHER NEW OR EXISTING- SECTION 107.2.1 WPB. |
| | |
| | 6) 1.0A AND PLUMBING PLAN: INDICATE HOW HOT WATER IS |
| | BEING PROVIDED TO THE MOP SINK, AND HOW TEMPERED WATER |
| | IS BEING PROVIDED TO THE LAVATORIES PER SECTIONS 416.5 |
| | & 607.1 FBC P. PLEASE NOTE THAT TEMPERED SHALL BE |
| | SUPPLIED THROUGH A WATER TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070- SECTION 607.1.2 FBC P. |
| | IT APPEARS THE DOOR INTO THE SMALLER OF THE TWO |
| | RESTROOMS WILL SWING INTO THE CLEAR FLOOR SPACE OF THE |
| | LAVATORY- SECTION 603.2.3 FBC ACC. |
| | |
| | 7) 1.0A: SHOW THE MANEUVERING CLEARANCES AT THE |
| | RESTROOM DOORS- REFER TO FIGURES 404.2.1 FBC ACC. |
| | PROVIDE DIMENSIONS ON THE PLAN TO VERIFY COMPLIANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |