| 2020-07-15 08:09:03 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20061121 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE CORRECT ADDRESS ON BOTH THE PLANS AND |
| | THE APPLICATION. THEY HAVE DIFFERENT ADDRESSES ON EACH |
| | AND I COULD NOT GET EITHER TO COME UP IN OUR GIS |
| | PROGRAM. FBC FS 107.2.1 |
| | |
| | 2) PLEASE PROVIDE A VENTILATION CALCULATION FOR EACH |
| | AREA OF TENANT SPACE. FBC M TABLE 403.3.1.1 |
| | |
| | 3) PLEASE PROVIDE INFORMATION ON EXISTING RTU?S WITH |
| | THE VENTILATION CALCULATIONS. FBC FS 107.2.1 |
| | |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |