Plan Review Notes
Plan Review Notes For Permit 20061121
Permit Number 20061121
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-07-02 10:29:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF TREATMENT ROOMS.
  
 FOR A REVIEW OF THE PROPER OCCUPANCY CLASSIFICATION PER
 NFPA 101, PLEASE PROVIDE A BRIEF DESCIPTION OF WHAT THE
 NATURE OF THE OCCUPANCY. WHAT IS THE NATURE OF THE
 BUSINESS?
  
  
  
 2) COVER SHEET & 1.1A - THERE IS AN INDICATION OF THE
 OCCUPANCY AS BUSINESS, WITH A SQ FT OF 3082, AND AN
 OCCUPANCY LOAD OF 31. BASED ON THAT INFORMATION PER
 NFPA 101 CHAPTER 7, TABLE 7.3.1.2 THE OCCUPANCY LOAD
 FACTOR IS 50SQ FT / PERSON OR 62.
  
 HOWEVER, THERE ARE INDICATION OF TWO SPACES/ROOMS
 INDICATED AS GYM ON SHEET 1.1A. PER THE SAME TABLE A
 GYM WITH NO EQUIPMENT HAS A FACTOR OF 15 SQ FT/PERSON.
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) SHEET 1.1A - THERE IS AN INDICATION OF THE FRONT
 EXIT PATH LEADING TO A DOOR THAT SWINGS IN. PER NFPA
 101, CH 7, THIS DOOR IS REQUIRED TO SWING IN THE PATH
 OF EGRESS.
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS
 THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS
 DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT.
  
  
 4) SHEET 1.1A - THE PLAN SHEET INDICATES A FRONT EXIT
 DOOR BUT IT DOES NOT INDICATE WHERE THAT FRONT EXIT
 LEADS TO OR WHETHER THAT IS A PROTECTED EXIT PATH TO
  
 PER NFPA 101 CH 7
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN
 7.7.1.2 THROUGH 7.7.1.4.
 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS
 OF THE EXIT
 DISCHARGE SHALL BE OF THE REQUIRED WIDTH AND SIZE TO
 PROVIDE ALL
 OCCUPANTS WITH A SAFE ACCESS TO A PUBLIC WAY.
 7.7.1.2 THE REQUIREMENT OF 7.7.1 SHALL NOT APPLY TO
 INTERIOR EXIT
 DISCHARGE AS OTHERWISE PROVIDED IN 7.7.2.
 7.7.2 EXIT DISCHARGE THROUGH INTERIOR BUILDING AREAS.
 EXITS SHALL
 BE PERMITTED TO DISCHARGE THROUGH INTERIOR BUILDING
 AREAS, PROVIDED
 THAT ALL OF THE FOLLOWING ARE MET:
 (1) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER OF
 EXIT STAIRS
 SERVING NORMALLY OCCUPIED AREAS OF EACH FLOOR, AND NOT
 MORE
 THAN 50 PERCENT OF THE EXIT STAIR CAPACITY REQUIRED FOR
 NORMALLY
 OCCUPIED AREAS OF EACH FLOOR, SHALL DISCHARGE THROUGH
 AREAS ON
 ANY LEVEL OF DISCHARGE, EXCEPT AS OTHERWISE PERMITTED
 BY ONE OF
 THE FOLLOWING:
 (A) ONE HUNDRED PERCENT OF THE EXITS SHALL BE PERMITTED
 TO
 DISCHARGE THROUGH AREAS ON ANY LEVEL OF DISCHARGE IN
 DETENTION AND CORRECTIONAL OCCUPANCIES AS OTHERWISE
 PROVIDED IN CHAPTERS 22 AND 23.
 (B) IN EXISTING BUILDINGS, THE 50 PERCENT LIMIT ON
 EGRESS
 CAPACITY SHALL NOT APPLY IF THE 50 PERCENT LIMIT ON THE
 REQUIRED NUMBER OF EXITS IS MET.
 (2) EACH LEVEL OF DISCHARGE SHALL DISCHARGE DIRECTLY
 OUTSIDE AT THE
 FINISHED GROUND LEVEL OR DISCHARGE DIRECTLY OUTSIDE AND
 PROVIDE
 ACCESS TO THE FINISHED GROUND LEVEL BY OUTSIDE STAIRS
 OR OUTSIDE
 RAMPS.
 (3) THE INTERIOR EXIT DISCHARGE SHALL LEAD TO A FREE
 AND UNOBSTRUCTED
 WAY TO THE EXTERIOR OF THE BUILDING, AND SUCH WAY SHALL
 BE READILY
 VISIBLE AND IDENTIFIABLE FROM THE POINT OF DISCHARGE
 FROM THE EXIT
 (4) THE INTERIOR EXIT DISCHARGE SHALL BE PROTECTED BY
 ONE OF THE
 FOLLOWING METHODS:
 (A) THE LEVEL OF DISCHARGE SHALL BE PROTECTED
 THROUGHOUT BY AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 9.7, OR THE PORTION OF THE LEVEL OF DISCHARGE
 USED FOR
 INTERIOR EXIT DISCHARGE SHALL BE PROTECTED BY AN
 APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7
 AND SHALL BE SEPARATED FROM THE NONSPRINKLERED PORTION
 OF
 THE FLOOR BY FIRE BARRIERS WITH A FIRE RESISTANCE
 RATING
 MEETING THE REQUIREMENTS FOR THE ENCLOSURE OF EXITS.
 (SEE
 7.1.3.2.1.)
 (B) THE INTERIOR EXIT DISCHARGE AREA SHALL BE IN A
 VESTIBULE OR
 FOYER THAT MEETS ALL OF THE FOLLOWING CRITERIA:
 I. THE DEPTH FROM THE EXTERIOR OF THE BUILDING SHALL BE
 NOT MORE THAN 10 FT (3050 MM), AND THE LENGTH SHALL
 BE NOT MORE THAN 30 FT (9.1 M).
 II. THE FOYER SHALL BE SEPARATED FROM THE REMAINDER OF
 THE
 LEVEL OF DISCHARGE BY FIRE BARRIERS WITH A MINIMUM 1-
 HOUR FIRE RESISTANCE RATING, AND EXISTING INSTALLATIONS
 OF
 WIRED GLASS IN STEEL FRAMES SHALL BE PERMITTED TO BE
 CONTINUED IN USE.
 III. THE FOYER SHALL SERVE ONLY AS MEANS OF EGRESS AND
 SHALL INCLUDE AN EXIT DIRECTLY TO THE OUTSIDE.
 (5) THE ENTIRE AREA ON THE LEVEL OF DISCHARGE SHALL BE
 SEPARATED FROM
 AREAS BELOW BY CONSTRUCTION HAVING A FIRE RESISTANCE
 RATING NOT
 LESS THAN THAT REQUIRED FOR THE EXIT ENCLOSURE, UNLESS
 OTHERWISE
 PROVIDED IN 7.7.2(6).
 (6) LEVELS BELOW THE LEVEL OF DISCHARGE IN AN ATRIUM
 SHALL BE
 PERMITTED TO BE OPEN TO THE LEVEL OF DISCHARGE WHERE
 SUCH LEVEL
 OF DISCHARGE IS PROTECTED IN ACCORDANCE WITH 8.6.7.
  
  
 PLEASE REVIEW, SHOW THE ENTIRE EXIT PATH ON THE PLAN
 SHEET AND PROVIDE FOR COMPLIANCE WITH THE REQUIREMENTS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  