| 2020-07-16 15:21:53 | 1ST REVIEW FBC-2017 RES. PLUMBING |
| | PERMIT- 20061112 |
| | 7/16/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P-1 & P-2: INDICATE THE DISTANCE FROM THE NEW |
| | SHOWER DRAIN TRAPS TO THE EXISTING VENTS DOES NOT |
| | EXCEED 8' PER SECTION AND TABLE P3105.1 FBC RES. |
| | OTHERWISE PROVIDE INDIVIDUAL VENTS. |
| | |
| | 2) P-1 & P-2: INDICATE HOW THE SUPPLY LINES TO THE |
| | DISHWASHER AND ICE MAKER WILL PROTECTED AGAINST |
| | BACKFLOW- SECTIONS P2717.1 & P2902.1 FBC RES. |
| | |
| | 3) PROVIDE SHOWER PAN DETAILS FOR THE NEW MASTER AND |
| | BEDROOM BATHS- SECTIONS P2709.1 & P2709.2 |
| | |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | TANKLESS WATER HEATERS- SECTION P2801.3. |
| | |
| | 5) THE NEW MASTER BATH TUB FAUCET SHALL BE IN |
| | COMPLIANCE WITH SECTIONS P2713.3 & P2902.4.2 . PLEASE |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE TUB VALVE |
| | AND THE NEW SHOWER VALVES- SECTION P2708.4. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |