2020-07-28 14:33:08PLAN REVIEW GENERATOR FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) GAS ISOMETRIC DRAWING: PROVIDE DETAIL OF GAS PIPING
 AT GENERATOR. INCLUDE SHUTOFF, DRIP LEG AND REGULATOR.
  
 1A) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR- SECTION G2421.1
  
 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH
 MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET
 AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION
 G2421.1.
  
  
  
  