| Plan Review Notes For Permit 20061111 |
| Permit Number |
20061111 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-28 14:33:08 | PLAN REVIEW GENERATOR FUEL GAS | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1) GAS ISOMETRIC DRAWING: PROVIDE DETAIL OF GAS PIPING | | | AT GENERATOR. INCLUDE SHUTOFF, DRIP LEG AND REGULATOR. | | | | | | 1A) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE | | | OUTLET OF THE REGULATOR- SECTION G2421.1 | | | | | | 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH | | | MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET | | | AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION | | | G2421.1. | | | | | | | | | | | | |
|