| 2020-10-13 10:44:30 | 3RD REVIEW FBC-2017 RES. PLUMBING |
| | PERMIT- 20061085 |
| | 10/13/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE PREVIOUS |
| | REVIEW LISTED BELOW WERE NOT ADDRESSED. NOTES HAVE BEEN |
| | ADDED. |
| | |
| | 1) THE 130 GPM PUMP FLOW DESIGN RATE EXCEEDS THE 125 |
| | GPM MAX FLOW RATE OF THE CS200 CARTRIDGE FILTER, AND |
| | THE 120 GPM MAX FLOW RATE OF THE SALT WATER |
| | CHLORINATOR- SECTION R4501.6 FBC RES. THE CS200 HAS |
| | BEEN REPLACED BY THE CS250 WHICH ALSO HAS 125 GPM FLOW |
| | RATE.NO CHANGES WERE MADE TO THE CHLORINATOR. |
| | |
| | 2) IDENTIFY ON THE SUBMITTED PUMP CURVE WHICH CURVE KEY |
| | IS SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL- |
| | SECTIONS- 4.4.9, 4.4.9.1. ANSI/APSP/ICC 7. PLEASE NOTE |
| | THAT THE MAX FLOW RATE OF THE PUMP FROM IT'S PUMP CURVE |
| | AND THE SIMPLIFIED TDH CALCULATION IS NO LONGER ALLOWED |
| | TO BE USED IN DETERMINING MAX FLOW RATE OF THE SYSTEM. |
| | |
| | 3) THE SPECS FOR THE FLOOR AND WALL CHANNEL DRAINS AND |
| | COVERS WERE NOT SUBMITTED- SECTION R4501.6.6 FBC RES, |
| | AND SECTIONS- 4.4.9, 4.4.9.1. ANSI/APSP/ICC 7. THE MAX |
| | SYSTEM FLOW RATE SHALL NOT EXCEED THE FLOW RATE OF THE |
| | SUCTION OUTLET FITTING ASSEMBLY. SPECS NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |