| 2020-09-21 15:28:02 | 2ND REVIEW FBC-2017 RES. PLUMBING |
| | PERMIT- 20061085 |
| | 9/21/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE 130 GPB PUMP FLOW DESIGN RATE EXCEEDS THE 125 |
| | GPM MAX FLOW RATE OF THE CS200 CARTRIDGE FILTER, AND |
| | THE 120 GPM MAX FLOW RATE OF THE SALT WATER |
| | CHLORINATOR- SECTION R4501.6 FBC RES. |
| | |
| | 2) IDENTIFY ON THE SUBMITTED PUMP CURVE WHICH CURVE KEY |
| | IS SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL- |
| | SECTIONS- 4.4.9, 4.4.9.1. ANSI/APSP/ICC 7. |
| | |
| | 3) THE SPECS FOR THE FLOOR AND WALL CHANNEL DRAINS AND |
| | COVERS WERE NOT SUBMITTED- SECTION R4501.6.6 FBC RES, |
| | AND SECTIONS- 4.4.9, 4.4.9.1. ANSI/APSP/ICC 7. THE MAX |
| | SYSTEM FLOW RATE SHALL NOT EXCEED THE FLOW RATE OF THE |
| | SUCTION OUTLET FITTING ASSEMBLY. |
| | |
| | 4) SHEET 4: INDICATE THE SIZE OF THE PIPES FROM THE |
| | INLET AND OUTLET OF THE PUMP TO THE 3-WAY VALVE |
| | DOWNSTREAM OF THE SALT GENERATOR- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |