2020-09-21 15:28:022ND REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20061085
 9/21/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE 130 GPB PUMP FLOW DESIGN RATE EXCEEDS THE 125
 GPM MAX FLOW RATE OF THE CS200 CARTRIDGE FILTER, AND
 THE 120 GPM MAX FLOW RATE OF THE SALT WATER
 CHLORINATOR- SECTION R4501.6 FBC RES.
  
 2) IDENTIFY ON THE SUBMITTED PUMP CURVE WHICH CURVE KEY
 IS SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL-
 SECTIONS- 4.4.9, 4.4.9.1. ANSI/APSP/ICC 7.
  
 3) THE SPECS FOR THE FLOOR AND WALL CHANNEL DRAINS AND
 COVERS WERE NOT SUBMITTED- SECTION R4501.6.6 FBC RES,
 AND SECTIONS- 4.4.9, 4.4.9.1. ANSI/APSP/ICC 7. THE MAX
 SYSTEM FLOW RATE SHALL NOT EXCEED THE FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY.
  
 4) SHEET 4: INDICATE THE SIZE OF THE PIPES FROM THE
 INLET AND OUTLET OF THE PUMP TO THE 3-WAY VALVE
 DOWNSTREAM OF THE SALT GENERATOR- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719