Plan Review Notes
Plan Review Notes For Permit 20061052
Permit Number 20061052
Review Stop B
Sequence Number 3
Notes
Date Text
2020-09-29 17:15:02WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061052
 ADD: 3200 ELECTRONICS WAY
 CONT: CLEAR SPAN STRUCTURES
 TEL: 561-803-8100 / GLENN BLOUNT
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: TUES. SEPT. 29TH/ 2020
 ACTION:
  
 1-4) COMPLIED.
 .
 4) 2ND REQUEST. THIS REVIEW THE NUCOR DRAWINGS PACKAGE
 OF 14 AND ONE OF 36 PLUS THE PRODUCT APPROVALS FOR THE
 ROOF AND WALL SYSTEMS. ROOF ZONE 3 IS 6 FEET 9 INCHES
 IN THE DIRECTION OF THE RIDGE.
 IN THE PACKAGE OF 36 PLANS PLAN 15 OF 36 IS THE ROOF
 PLAN WITH ROOF ZONES. SHEET 9 OF 14 SET OF PLANS SHOWS
 THE ROOF PURLIN SPACING. THE SPACING STARTS FROM THE
 EDGE OF THE ROOF WITH 2 FEET TO THE NEXT PURLIN THEN A
 SPACE OF 3 FEET 9 INCHES AND A SECOND SPACE OF 3 FEET
 NINE INCHES.
  
 THE ROOFING PRODUCT APPROVAL FL. 4891.1-R8 PAGE 2 OF 3
 INDICATES THE ROOFING SYSTEMS (3) WITH VICE LOCK 360
 WITH SUPPORTS AT 24 INCHES ON CENTER IS GOOD FOR 108.8
 PSF. THE SAME VISE LOCK 360 WITH SUPPORTS AT 5FEET IS
 GOOD FOR 59.3PSF. IT WOULD APPEAR ANOTHER PURLIN IS
 NEEDED IN THE CORNER OF THE BUILDING FOR ROOF ZONE 3.
 THE SAME SITUATION MAY OCCUR IN WALL ZONE 5 THE WALL
 END ZONE. SHEET 11OF 36, SHEET 9 OF 14 AND PRESSURES
 FOR THE END ZONE DO NOT MAKE IT. PLEASE ALSO NOTE THE
 SHOP DRAWING STAMP OF APPROVAL BLOCKS OUT THE BOTTOM
 SPAN ON ALL SHEETS RIGHT SIDE OF THE BUILDING, ASSUMING
 THE LEFT SIDE WILL HAVE THE SAME SPACING.
 CALLED NUCOR ABOUT THIS ISSUE, SPOKE TO RUSS MILFORD
 PROJECT MANAGER HE SAID THE ENGINEER ANDREW JOHNSON
 WOULD GET BACK TO ME.
  
 5) BUILDING PROVISO: BUILDINGS WITH WELDED OR BOLTED
 CONNECTIONS, THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 BUILDING PROVISO:6) DELEGATED ENGINEERING. 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
  
 7-9) COMPLIED.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  