| 2020-08-31 17:24:36 | ROOF REVIEW: 2ND REVIEW, NO PLANS SHOWING THE SPACING | | | OF THE PURLINS IN THE ROOF ZONES 1,2,NOR 3 AND THIS | | | REVIEW (2ND) NO ROOFING PRODUCT APPROVAL IDENTIFYING | | | THE ROOFING MATERIAL, WIDTH OF PANEL, TYPE, GAUGE METAL | | | ALLOWABLE SPANS AND TYPE OF ROOF ANCHORS!!!!!!!!SEE | | | BUILDING COMMENTS. |
|