| 2020-08-31 17:20:48 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20061052 |
| | ADD: 3200 ELECTRONICS WAY |
| | CONT: CLEAR SPAN STRUCTURES |
| | TEL: 561-803-8100 / GLENN BLOUNT |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: MON. AUGUST 31ST/ 2020 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!!!! 4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B) |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) SEMI-COMPLIED, 2ND REQUEST. THE RESPONSE LETTER |
| | STATES THE PERMITTED USE OF THE SITE PLAN APPROVAL AS |
| | INDUSTRIAL. I BELIEVE THAT YOU ARE INDICATING THE SITE |
| | PLAN APPROVAL PROCESS KNOWN AS PPRC. THIS IS A ZONING |
| | REQUIREMENT. I AM NOT REVIEWING FOR ZONING REGULATIONS |
| | BUT UNDER THE 2017 FLORIDA BUILDING CODE FOR THE |
| | STRUCTURE AND FUTURE USE ONCE THE BUILDING HAS ITS |
| | CERTIFICATE OF OCCUPANCY. TO MEET BOTH CODES YOU WILL |
| | NEED TO IDENTIFY UNDER WHICH CODE YOU ARE DESCRIBING |
| | THE BUILDING. IT IS COMMON FOR DAYCARE OCCUPANCIES TO |
| | HAVE THE DOUBLE COMMON, ONE FOR THE STATE REQUIREMENTS |
| | AND ONE FOR THE THE REQUIREMENTS FOUND IN THE BUILDING |
| | CODE. I WOULD SUGGEST THIS IS A WAY TO SATISFY BOTH THE |
| | ZONING REQUIREMENTS AS WELL AS THE 2017 FBC-BUILDING |
| | REQUIREMENTS. |
| | 1ST REVIEW. THERE IS A DISCREPANCY IN OCCUPANCY |
| | CLASSIFICATION FOR THIS BUILDING. THE SITE PLAN SHEET |
| | LIST THE OCCUPANCIES AS INDUSTRIAL & BUSINESS WHEREAS |
| | THE LIFE SAFETY SHEET INDICATES THE OCCUPANCIES TO BE |
| | S2 STORAGE AND BUSINESS OCCUPANCY. 107.2.1.2. |
| | ADDITIONAL INFORMATION IS REQUIRED, DISCREPANCY IN |
| | PLANS. |
| | |
| | 2) COMPLIED, NOT IN AN A FLOOD ZONE. |
| | 3) COMPLIED |
| | . |
| | 4) 2ND REQUEST. SHEET S-4.0 SHOWS ONLY THE BLOCK |
| | EXTERIOR WALL. THERE ARE NO STRUCTURAL SHEETS SUBMITTED |
| | FOR THE METAL FRAME BUILDING, SHOWING THE BUILDING |
| | ELEVATIONS WITH THE SPACING OF THE HORIZONTAL GIRTS AND |
| | PURLINS. COMPLIANCE WITH THE EXTERIOR WALL AND ROOF |
| | FASTENING SYSTEM CANNOT BE REVIEWED. THE MISSING |
| | INFORMATION THE PRODUCT APPROVAL FOR THE METAL EXTERIOR |
| | WALL SYSTEM AND METAL ROOF SYSTEM. WITHOUT THE PRODUCT |
| | APPROVALS BEING SUBMITTED, IDENTIFYING THE TYPE OF WALL |
| | AND ROOF PANELS BEING INSTALLED, WITH THEIR ALLOWABLE |
| | SPACING BETWEEN SUPPORTS (GIRTS & PURLINS) AND |
| | ASSOCIATED PRESSURES NO REVIEW FOR THE STRUCTURAL |
| | PORTION OF THE BUILDING CAN BE COMPLETED. |
| | |
| | 5) COMPLIED. BUILDINGS WITH WELDED OR BOLTED |
| | CONNECTIONS, THE CONTRACTOR IS REQUIRED TO PROVIDE WELD |
| | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT |
| | 561-805-6666. |
| | |
| | 6A)2ND REQUEST. THE 2ND REVIEW CYCLE NO WALL NOR |
| | ROOFING PRODUCT APPROVALS WERE SUBMITTED!!!!!!!! |
| | COMPONENTS & CLADDING PLEASE SUPPLY THE PRODUCT |
| | APPROVAL FULL REPORTS. IF IN THE PRODUCT APPROVAL THERE |
| | ARE MULTIPLE SUB-SYSTEMS APPROVED IDENTIFY (CIRCLE) |
| | WHICH APPLICATION IS TO BE INSTALLED. |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: METAL WALL PANELS, STOREFRONTS, |
| | CURTAIN WALLS, WALL LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, METAL ROOF PANELS, |
| | LIGHTWEIGHT CONCRETE INSULATION, ROOF TOP VENTILATORS |
| | |
| | 6B) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6C) 2ND REQUEST. DELEGATED ENGINEERING. 61G15-30.003 |
| | ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006 |
| | (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 7) 2ND REQUEST. THE OTHER UNKNOWN IS IF THE ENGINEER OF |
| | RECORD FOR THE METAL BUILDING MANUFACTURER HAS DESIGNED |
| | THE ROOF SYSTEM TO SECTION 2211.5 OF THE FBC-B AISI |
| | S210 OR AISI S 100? WITH A GREATER DEDUCTION IN |
| | PRESSURES ALONG WITH THE DEDUCTION FROM VULT TO VASD? |
| | |
| | 8) ADA DETAILS SHEET ADA 1.1: |
| | |
| | 8-9) COMPLIED. |
| | |
| | 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION (PRODUCT APPROVALS). WITH THE NEXT PLAN |
| | REVIEW CYCLE THERE MAYBE ADDITIONAL REVIEW COMMENTS |
| | BECAUSE OF NEW PLANS AND INFORMATION LACKING UNDER THE |
| | PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |