| Plan Review Notes For Permit 20061052 |
| Permit Number |
20061052 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-31 08:06:01 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E.2 | | | | | | 1) SERVICE SHOWS MAIN BREAKER PANEL CONDUCTORS FROM | | | METER TO PANEL HAVE TO ROUTED OUTSIDE OF THE BUILDING | | | IF MORE THAN 8' OF CO NDUCTOR IS TO BE USED. | | | | | | 2) CIRCUIT A-29 TO BE GFCI PROTECTED TO DRINKING | | | FOUNTAIN. 422.52 | | | | | | 3) BREAK ROOM OUTLETS WITHIN 6' OF THE SINK TO BE GFCI | | | PROTECTED 210.8(B) | | | | | | PAGE E.4 | | | | | | 1) LOAD CALCULATION LIGHTING LOAD NOT PER 220.12 SEE | | | TABLE 220,12 | | | | | | 2) AIC RATING OF MAIN AND PANEL REQUIRED PER 110.9, | | | 110,10 AND LABELED PER 110.24 | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | | | | 3) PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | | SERVICE. NEC 250.94 | | | | | | |
|