2020-07-31 08:06:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.2
  
 1) SERVICE SHOWS MAIN BREAKER PANEL CONDUCTORS FROM
 METER TO PANEL HAVE TO ROUTED OUTSIDE OF THE BUILDING
 IF MORE THAN 8' OF CO NDUCTOR IS TO BE USED.
  
 2) CIRCUIT A-29 TO BE GFCI PROTECTED TO DRINKING
 FOUNTAIN. 422.52
  
 3) BREAK ROOM OUTLETS WITHIN 6' OF THE SINK TO BE GFCI
 PROTECTED 210.8(B)
  
 PAGE E.4
  
 1) LOAD CALCULATION LIGHTING LOAD NOT PER 220.12 SEE
 TABLE 220,12
  
 2) AIC RATING OF MAIN AND PANEL REQUIRED PER 110.9,
 110,10 AND LABELED PER 110.24
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 3) PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
  
  