| Plan Review Notes For Permit 20061038 |
| Permit Number |
20061038 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-24 11:51:54 | PLAN REVIEW GENERATOR - BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | 1) PROVIDE SITE SPECIFIC WIND LOAD DESIGN PRESSURE | | | CALCULATIONS FOR THE GENERATOR PER FBC 107.3.5.3 AND | | | R301.2 AND AS REQUIRED PER THE GENERATOR PAD | | | ENGINEERING. CANNOT VERIFY IF GENERATOR PAD WIND LOADS | | | ARE ADEQUATE. | | | | | | 2) SHOW LOCATION OF PROPOSED GENERATOR ON SURVEY. | | | PROVIDE SETBACKS TO STRUCTURE, BUILDING OPENINGS AND | | | PROPERTY LINES PER 107.2 CONSTRUCTION DOCUMENTS | | | |
|