Plan Review Notes
Plan Review Notes For Permit 20061036
Permit Number 20061036
Review Stop P
Sequence Number 1
Notes
Date Text
2020-06-30 16:14:341ST REVIEW FBC-2017 PLUMBING
 PERMIT-20061036
 6/30/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPROVED DEMOLITION PLAN UNDER PERMIT #20050101
 INDICATES A TOILET ROOM WAS REMOVED, HOWEVER THE
 BUILD-OUT PLAN DOES NOT INDICATE THE ROOM AND PLUMBING
 FIXTURES ARE BEING REPLACED. PLEASE PROVIDE PLUMBING
 FIXTURE CALCULATIONS FOR THE 3RD FLOOR IN ACCORDANCE
 WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE INDICATING
 THE REQUIRED AND PROVIDED FIXTURES ON THE FLOOR-
 SECTION 213.1 FBC ACC.
  
 2) SHEET P1 & P2: SHOW THE LOCATION OF THE THERMOSTATIC
 MIXING VALVE THAT IS LISTED IN THE FIXTURE SCHEDULE-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  